APPENDIX B - VFD INFORMATION (CONT)

Main Fan Replacement

The main cooling fan of the VFD has a life span of about 60,000

operating hours at maximum rated operating temperature and drive
load. The expected life span doubles for each 18 F drop in the fan

temperature (fan temperature is a function of ambient temperatures
and drive loads).
Fan failure can be predicted by the increasing noise from fan
bearings and the gradual rise in the heat sink temperature in spite of

heat sink cleaning. If the drive is operated in a critical part of a

process, fan replacement is recommended once these symptoms
start appearing. Replacement fans are available from Carrier.
To replace the main fan for frame sizes R1 through R2, perform the
following (see Main Fan Replacement figure):

1. Remove power from drive.
2. Remove drive cover.
3. For frame sizes R1 and R2, press together the retaining clips

on the fan cover and lift.

4. Disconnect the fan cable.
5. Install the new fan by reversing Steps 2 to 4.
6. Restore power.

3

3

4

2

C08681

Fig. 43 -- Main Fan Replacement

(Frame Sizes R1--R2)

Control Panel Cleaning

Use a soft damp cloth to clean the control panel. Avoid harsh

cleaners which could scratch the display window.

Battery Replacement

A battery is only used in assistant control panels that have the clock

function available and enabled. The battery keeps the clock

operating in memory during power interruptions. The expected life
for the battery is greater than ten years. To remove the battery, use

a coin to rotate the battery holder on the back of the control panel.
Replace the battery with type CR2032.