CONTROL SET POINT AND CONFIGURATION LOG

Model Number: _____________________________
Serial Number: ______________________________
Date: ______________________________________
Technician: _________________________________

Software Versions: ___________________________
MBB: CESR131320---- _ _
ECB: CESR131249---- _ _
MARQ: CESR131171---- _ _

INDICATE UNIT SETTINGS BELOW

Control Type:

Thermostat/T55 Space Temp./T--56 Space Temp./T--58 Space Temp.

Set Points:

Cooling

Occupied: _______________

Unoccupied: __________________

Heating

Occupied: _______________

Unoccupied: __________________

Table 65 — MODE - CONFIGURATION

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN

TABLE/SUB---TABLE

CCN POINT

ENTRY

CONFIGURATION

SERVICE

CONFIGURATION

DISP

Display Configuration

DISPLAY

METR

Metric Display

On/Off

Off

DISPUNIT

LANG

Language Selection

0=English

1=Spanish

2=French

3=Portuguese

0

LANGUAGE

PROT

Password Enable

Enable/Disable

Disable

PASS_EBL

PSWD

Service Password

0000 to 9999

1111

PASSWORD

TEST

Test Display LEDs

On/Off

Off

(display only, not in

table)

DISPTEST

UNIT

Unit Configuration

UNIT

S.DLY

Startup Delay

0 to 600

sec

30

STARTDLY

OC.FN

Fan On When Occupied

Yes/No

Yes

OCC_FAN

IDF.F

Shut Down on IDF Failure

Yes/No

Yes

FATALFAN

FS.MX

Supply Fan Maximum

Speed

80 to 100

%

100

SPEEDMAX

FS.MN

Supply Fan Minimum Speed

10 to 40

%

20

SPEEDMIN

FS.VM

Vent Mode Fan Speed

40 to 100

^F

50

SPEEDVNT

FN.SW

Fan Status Switch

0=No Switch

1=Normal Open

2=Normal Closed

0: no FIOP

1: FIOP

FANSTCFG

FL.SW

Filter Status Switch

0=No Switch

1=Normal Open

2=Normal Closed

0: no FIOP

1: FIOP

FILSTCFG

FS.SW

Fire Shutdown Switch

0=No Switch

1=Normal Open

2=Normal Closed

0: no FIOP

1: FIOP

SHTDNCFG

RM.SW

Remote Occupancy Switch

0=No Switch

1=Normal Open

2=Normal Closed

0

REMOCCFG

RH.S

RH Sensor on OAQ Input

Yes/No

No

RH_OAQ

RH.SW

Space Humidity Switch

0=No Switch

1=Normal Open

2=Normal Closed

0

HUMSTCFG

TCS.C

Temp Cmp Strt Cool Factr

0 to 60

mins

0

TCSTCOOL

TCS.H

Temp Cmp Strt Heat Factr

0 to 60

mins

0

TCSTHEAT

COOL

Cooling Configuration

COOL_CFG

MIN.C

Min Compressor Capacity

15 to 80

%

70

MIN_CAPC

FS.CD

Fan Speed Control Demand

1 to 9.9

^F

3

SPEEDDMD

MRT.C

Compressor Min On Time

120 to 999

sec

180

MIN_ON

MOT.C

Compressor Min Off Time

300 to 999

sec

300

MIN_OFF

RST.C

Runtime to Reset Strikes

120 to 999

sec

300

MIN_ON_S

FOD.C

Fan--- off Delay, Mech Cool

0 to 600

sec

60

COOL_FOD

CS.A1

Current Sensing A1

Enable/Disable

Disable: reserved for

future use

DO NOT ENABLE

A1_SENSE

C.LO

Compressor Lockout Temp

0 to 100F

dF

0

OATLCOMP

ALM.N

Alert Each Strike

Yes//No

Yes

ALM_NOW

SAT

Supply Air Temperature

SASP

Cool Supply Air Setpoint

45 to 75

dF

65

SASP

SA.MU

SASP Maximum Reset Up

0 to 20

^F

10

SASPMAXU

SA.MD

SASP Maximum Reset

Down

--- 20 to 0

^F

--- 10

SASPMAXD

SAT.U

Minimum SAT Upper Level

35.0 to 65.0

dF

60

SATMIN_H

SAT.L

Minimum SAT Lower Level

35.0 to 65.0

dF

45

SATMIN_L

SST

Low Suction Control

SST.O

Suction OK Temperature

10 to 50

dF

18

SSTOK

SST.1

Low Suction --- Level 1

10 to 50

dF

20

SSTLEV1

SST.2

Low Suction --- Level 2

5 to 50

dF

15

SSTLEV2

SST.3

Low Suction --- Level 3

0 to 50

dF

10

SSTLEV3

PSI.D

Ckt A Minimum Pressure

0 to 500

psig

20

DELTAP_A

OFC

Outdoor Fan Control

1.MXP

Fan Lev1 Max Pressure

100 to 500

psig

450

LEV1MAXP

2.MNP

Fan Lev2 Min Pressure

100 to 500

psig

200

LEV2MINP

2.ON

Fan Lev2 On Temperature

0 to 100

F

55

LEV2ON

2.OFF

Fan Lev2 Off Temperature

0 to 100

F

45

LEV2OFF

48/

50P

D