Control set point and configuration log, Indicate unit settings below, 48/ 50p d – Carrier 48/50PD05 User Manual
Page 101

101
CONTROL SET POINT AND CONFIGURATION LOG
Model Number: _____________________________
Serial Number: ______________________________
Date: ______________________________________
Technician: _________________________________
Software Versions: ___________________________
MBB: CESR131320---- _ _
ECB: CESR131249---- _ _
MARQ: CESR131171---- _ _
INDICATE UNIT SETTINGS BELOW
Control Type:
Thermostat/T55 Space Temp./T--56 Space Temp./T--58 Space Temp.
Set Points:
Cooling
Occupied: _______________
Unoccupied: __________________
Heating
Occupied: _______________
Unoccupied: __________________
Table 65 — MODE - CONFIGURATION
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN
TABLE/SUB---TABLE
CCN POINT
ENTRY
CONFIGURATION
SERVICE
CONFIGURATION
DISP
Display Configuration
DISPLAY
METR
Metric Display
On/Off
Off
DISPUNIT
LANG
Language Selection
0=English
1=Spanish
2=French
3=Portuguese
0
LANGUAGE
PROT
Password Enable
Enable/Disable
Disable
PASS_EBL
PSWD
Service Password
0000 to 9999
1111
PASSWORD
TEST
Test Display LEDs
On/Off
Off
(display only, not in
table)
DISPTEST
UNIT
Unit Configuration
UNIT
S.DLY
Startup Delay
0 to 600
sec
30
STARTDLY
OC.FN
Fan On When Occupied
Yes/No
Yes
OCC_FAN
IDF.F
Shut Down on IDF Failure
Yes/No
Yes
FATALFAN
FS.MX
Supply Fan Maximum
Speed
80 to 100
%
100
SPEEDMAX
FS.MN
Supply Fan Minimum Speed
10 to 40
%
20
SPEEDMIN
FS.VM
Vent Mode Fan Speed
40 to 100
^F
50
SPEEDVNT
FN.SW
Fan Status Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
FANSTCFG
FL.SW
Filter Status Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
FILSTCFG
FS.SW
Fire Shutdown Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG
RM.SW
Remote Occupancy Switch
0=No Switch
1=Normal Open
2=Normal Closed
0
REMOCCFG
RH.S
RH Sensor on OAQ Input
Yes/No
No
RH_OAQ
RH.SW
Space Humidity Switch
0=No Switch
1=Normal Open
2=Normal Closed
0
HUMSTCFG
TCS.C
Temp Cmp Strt Cool Factr
0 to 60
mins
0
TCSTCOOL
TCS.H
Temp Cmp Strt Heat Factr
0 to 60
mins
0
TCSTHEAT
COOL
Cooling Configuration
COOL_CFG
MIN.C
Min Compressor Capacity
15 to 80
%
70
MIN_CAPC
FS.CD
Fan Speed Control Demand
1 to 9.9
^F
3
SPEEDDMD
MRT.C
Compressor Min On Time
120 to 999
sec
180
MIN_ON
MOT.C
Compressor Min Off Time
300 to 999
sec
300
MIN_OFF
RST.C
Runtime to Reset Strikes
120 to 999
sec
300
MIN_ON_S
FOD.C
Fan--- off Delay, Mech Cool
0 to 600
sec
60
COOL_FOD
CS.A1
Current Sensing A1
Enable/Disable
Disable: reserved for
future use
DO NOT ENABLE
A1_SENSE
C.LO
Compressor Lockout Temp
0 to 100F
dF
0
OATLCOMP
ALM.N
Alert Each Strike
Yes//No
Yes
ALM_NOW
SAT
Supply Air Temperature
SASP
Cool Supply Air Setpoint
45 to 75
dF
65
SASP
SA.MU
SASP Maximum Reset Up
0 to 20
^F
10
SASPMAXU
SA.MD
SASP Maximum Reset
Down
--- 20 to 0
^F
--- 10
SASPMAXD
SAT.U
Minimum SAT Upper Level
35.0 to 65.0
dF
60
SATMIN_H
SAT.L
Minimum SAT Lower Level
35.0 to 65.0
dF
45
SATMIN_L
SST
Low Suction Control
SST.O
Suction OK Temperature
10 to 50
dF
18
SSTOK
SST.1
Low Suction --- Level 1
10 to 50
dF
20
SSTLEV1
SST.2
Low Suction --- Level 2
5 to 50
dF
15
SSTLEV2
SST.3
Low Suction --- Level 3
0 to 50
dF
10
SSTLEV3
PSI.D
Ckt A Minimum Pressure
0 to 500
psig
20
DELTAP_A
OFC
Outdoor Fan Control
1.MXP
Fan Lev1 Max Pressure
100 to 500
psig
450
LEV1MAXP
2.MNP
Fan Lev2 Min Pressure
100 to 500
psig
200
LEV2MINP
2.ON
Fan Lev2 On Temperature
0 to 100
F
55
LEV2ON
2.OFF
Fan Lev2 Off Temperature
0 to 100
F
45
LEV2OFF
48/