Appendix a - local display and ccn tables (cont) – Carrier 48/50PD05 User Manual
Page 69

69
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 27 — MODE - RUN STATUS (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN
TABLE/SUB---TABLE
CCN POINT
CCN WRITE
STATUS
STRT
Component Starts
A1
Compressor A1 Starts
xxxxxx
ST_A1
forcible
CCH
Crankcase Heater Starts
xxxxxx
ST_CCH
forcible
IDF
Indoor Fan Starts
xxxxxx
ST_IDF
forcible
OFC.1
Outdoor Fan 1 Starts
xxxxxx
ST_OFC_1
forcible
HT.1
Heat Stage 1 Starts
xxxxxx
ST_HTR_1
forcible
HT.2
Heat Stage 2 Starts
xxxxxx
ST_HTR_2
forcible
PE.1
Power Exhaust 1 Starts
xxxxxx
ST_PE_1
forcible
PE.2
Power Exhaust 2 Starts
xxxxxx
ST_PE_2
forcible
ALRM
Alarm Relay Starts
xxxxxx
ST_ALM
forcible
(ALRMDISP) = CCN
only)
ALRMDISP
Active Alarm 1 Code
xxx
ALMCODE1
Active Alarm 2 Code
xxx
ALMCODE2
Active Alarm 3 Code
xxx
ALMCODE3
Active Alarm 4 Code
xxx
ALMCODE4
Active Alarm 5 Code
xxx
ALMCODE5
Reset All Current Alarms
Yes/No
ALRESET
forcible
Reset Alarm History
Yes/No
ALHISCLR
forcible
(GENERIC = CCN
only)
GENERIC
up to 20 points
(LON_DATA = CCN
only)
LON_DATA
nviSpaceTemp
xxx.x
dF
NVI_SPT
forcible
nviSetPoint
xxx.x
dF
NVI_SP
forcible
nvoSpaceTemp
xxx.x
dF
NVO_SPT
nvoUnitStatus.mode
xxxx
NVO_MODE
nvoUnitStatus.heat_out_p
xxx.x
%
NVO_HPRI
nvoUnitStatus.heat_out_s
xxx.x
%
NVO_HSEC
nvoUnitStatus.cool_out
xxx.x
%
NVO_COOL
nvoUnitStatus.econ_out
xxx.x
%
NVO_ECON
nvoUnitStatus.fan_out
xxx
%
NVO_FAN
nvoUnitStatus.in_alarm
xxx
NVO_ALRM
nviSetPtOffset
xxx.x
^F
NVI_SPTO
forcible
nviOutsideTemp
xxx.x
dF
NVI_OAT
forcible
nviOutsideRH
xxxx.x
%
NVI_OARH
forcible
nvoEffectSetPt
xxx.x
dF
NVO_EFSP
nvoOutsideTemp
xxxx.x
dF
NVO_OAT
nvoOutsideRH
xxx.x
%
NVO_OARH
nviSpaceRH
xxx.x
%
NVI_SPRH
forcible
nviCO2
xxxxx
NVI_CO2
forcible
nvoCO2
xxxxx
NVO_CO2
nvoTEMP1
xxx.x
dF
NVO_SAT
nvoTEMP2
xxx.x
dF
NVO_RAT
nviPCT1
xxx.x
%
NVI_RHSP
forcible
nvoPCT1
xxx.x
%
NVO_SPRH
nviDISCRETE1
Off/On
NVI_FSD
forcible
nviDISCRETE2
No/Yes
NVI_OCC
forcible
nviDISCRETE3
Off/On
NVI_IAQD
forcible
nvoDISCRETE1
Off/On
NVO_FSD
nvoDISCRETE2
No/Yes
NVO_OCC
nvoDISCRETE3
Off/On
NVO_IAQD
nciCO2Limit
xxxxx
NCI_CO2
forcible
nciSetPnts.occupied_cool
xxx.x
dF
NCI_OCSP
forcible
nciSetPnts.standby_cool
xxx.x
dF
NCI_SCSP
forcible
nciSetPnts.unoccupd_cool
xxx.x
dF
NCI_UCSP
forcible
nciSetPnts.occupied_heat
xxx.x
dF
NCI_OHSP
forcible
nciSetPnts.standby_heat
xxx.x
dF
NCI_SHSP
forcible
nciSetPnts.unoccupd_heat
xxx.x
dF
NCI_UHSP
forcible