APPENDIX A - LOCAL DISPLAY AND CCN TABLES

Table 27 — MODE

- RUN STATUS

ITEM

EXPANSION

RANGE

UNITS

CCN

TABLE/SUB---TABLE

CCN POINT

CCN WRITE

STATUS

RUN STATUS

STATUS DISPLAY

VIEW

Auto View of Run Status

(VIEW = Display only)

HVAC

HVAC Mode Status

1=Disabled

2=Fan Only

3=Cool

4=Heat

HVACMODE

OCC

Currently Occupied

Yes/No

OCCUPIED

SAT

Supply Air Temperature

xxx..x

dF

SAT_DISP

ALRM

Current Alarms & Alerts

xx

ALRMALRT

TIME

Time of Day

xx.xx

hh.mm

TIMECOPY

VERS

Software Version Numbers

VERSIONS

MBB

CESR131459--- xx--- xx

(xx--- xx in

table)

MODEL_NUMBER_01

ECB

CESR131249--- xx--- xx

MODEL_NUMBER_02

AUX

CESR131333--- xx--- xx

MODEL_NUMBER_03

MARQ

CESR131171--- xx--- xx

MODEL_NUMBER_04

MODE

Control Modes

MODEDISP

SYS

Unit operation disabled

Unit operation enabled

Service test enabled

SYS_MODE_TEXT1

SYS_MODE_TEXT2

(table only)

SYS_MODE_TEXT3

(table only)

HVAC

HVAC Operation Disabled

Ventilation (fan--- only)

Cooling

Unoccupied Free Cooling

Heating

HVACMODE_TEXT_1

HVACMODE_TEXT_2

(table only)

HVACMODE_TEXT_3

(table only)

HV.DN

Remote HVAC Mode Disable

Yes/No

HVACDOWN

forcible

EFF.C

Cool Setpoint in Effect

xxx.x

CSP_EFF

EFF.H

Heat Setpoint in Effect

xxx.x

HSP_EFF

OCC

Currently Occupied

Yes/No

OCCUPIED

forcible

T.OVR

Timed Override in Effect

Yes/No

MODETOVR

LINK

Linkage Active

Yes/No

MODELINK

D.LMT

Demand Limit In Effect

Yes/No

MODEDMDL

C.LOC

Compressor OAT Lockout

Yes/No

COMPLOCK

H.LOC

Heat OAT Lockout

Yes/No

HEATLOCK

E.LOC

Econo Cool OAT Lockout

Yes/No

ECONLOCK

COOL

Cooling Status

COOLDISP

DMD.C

Cooling Demand

xxx.x

^F

COOL_DMD

SA.CP

Supply Air Control Point

xxx.x

dF

SA_CTLPT

SASP

Cool Supply Air Setpoint

xxx.x

dF

SASP

SR.CD

Cool Demand SASP Reset

xxx.x

^F

CD_RESET

SR.RH

Dehumidifying SASP Reset

xxx.x

^F

RH_RESET

F.SPD

Commanded Fan Speed

xxx

%

FANSPEED

CMP.A

Compressor A Feedback

On/Off

COMP_A

TG.A

Compressor A Timeguard

xxx

sec

TIMGD_A

CAPC

Compressor Capacity

xxx

%

CAPACITY

MAX.C

Max Compressor Capacity

xxx

%

MAX_CAPC

forcible

MIN.C

Min Compressor Capacity

xxx

%

MIN_CAPC

LMT.C

Max Capacity In Effect

xxx

%

CAPLIMIT

SST.A

Sat. Suction Temp A

xxx.x

dF

SST_A

SSP.A

Suction Pressure A

xxx.x

psig

SSP_A

SCT.A

Sat. Condenser Temp A

xxx.x

dF

SCT_A

SCP.A

Condenser Pressure A

xxx.x

psig

SCP_A

OFC.1

Outdoor Fan 1 Relay

On/Off

OFC_1

HEAT

Heating Status

HEATDISP

DMD.H

Heating Demand

xxx.x

^F

HEAT_DMD

AVL.H

Available Heating Stages

x

AVLHSTGS

REQ.H

Requested Heating Stages

x

REQHSTGS

MAX.H

Max Allowed Heat Stages

x

MAXHSTGS

forcible

LMT.H

Max Heat Stage In Effect

x

HSTGLIMT

F.SPD

Commanded Fan Speed

xxx

%

FANSPEED

HT.1

Heat Stage 1 Relay

On/Off

HEAT_1

TG.H1

Heat Stage 1 Timequard

xxx

sec

TIMGD_H1

HT.2

Heat Stage 2 Relay

On/Off

HEAT_2

TG.H2

Heat Stage 2 Timequard

xxx

sec

TIMGD_H2

ECON

Economizer Status

ECONDISP

EC.CP

Econo Commanded Position

xxx

%

ECONOCMD

EC.AP

Econo Actual Position

xxx

%

ECONOPOS

EC.MP

Min Position in Effect

xxx

%

MIN_POS

IAQ.S

IAQ Level (switch)

High/Low

IAQIN

IAQ

IAQ Level (sensor)

xxxx

ppm

IAQ

OAT

Outdoor Air Temperature

xxx.x

dF

OA_TEMP

ENTH

Outdoor Enthalpy Switch

High/Low

ENTHALPY

OAQ

OAQ Level (sensor)

xxxx

ppm

OAQ

PE.1

Power Exhaust 1 Relay

On/Off

PE_1

PE.2

Power Exhaust 2 Relay

On/Off

PE_2

HRS

Component Run Hours

STRTHOUR

A1

Compressor A1 Run Hours

xxxxx.xx

hours

HR_A1

forcible

CCH

Crankcase Htr Run Hours

xxxxx.xx

hours

HR_CCH

forcible

IDF

Indoor Fan Run Hours

xxxxx.xx

hours

HR_IDF

forcible

OFC.1

Outdoor Fan 1 Run Hours

xxxxx.xx

hours

HR_OFC_1

forcible

HT.1

Heat Stage 1 Run Hours

xxxxx.xx

hours

HR_HTR_1

forcible

HT.2

Heat Stage 2 Run Hours

xxxxx.xx

hours

HR_HTR_2

forcible

PE.1

Power Exhaust1 Run Hours

xxxxx.xx

hours

HR_PE_1

forcible

PE.2

Power Exhaust2 Run Hours

xxxxx.xx

hours

HR_PE_2

forcible

ALRM

Alarm Relay Run Hours

xxxxx.xx

hours

HR_ALM

forcible