APPENDIX A - LOCAL DISPLAY AND CCN TABLES
Table 27 — MODE
- RUN STATUS
ITEM
EXPANSION
RANGE
UNITS
CCN
TABLE/SUB---TABLE
CCN POINT
CCN WRITE
STATUS
RUN STATUS
STATUS DISPLAY
VIEW
Auto View of Run Status
(VIEW = Display only)
HVAC
HVAC Mode Status
1=Disabled
2=Fan Only
3=Cool
4=Heat
HVACMODE
OCC
Currently Occupied
Yes/No
OCCUPIED
SAT
Supply Air Temperature
xxx..x
dF
SAT_DISP
ALRM
Current Alarms & Alerts
xx
ALRMALRT
TIME
Time of Day
xx.xx
hh.mm
TIMECOPY
VERS
Software Version Numbers
VERSIONS
MBB
CESR131459--- xx--- xx
(xx--- xx in
table)
MODEL_NUMBER_01
ECB
CESR131249--- xx--- xx
MODEL_NUMBER_02
AUX
CESR131333--- xx--- xx
MODEL_NUMBER_03
MARQ
CESR131171--- xx--- xx
MODEL_NUMBER_04
MODE
Control Modes
MODEDISP
SYS
Unit operation disabled
Unit operation enabled
Service test enabled
SYS_MODE_TEXT1
SYS_MODE_TEXT2
(table only)
SYS_MODE_TEXT3
(table only)
HVAC
HVAC Operation Disabled
Ventilation (fan--- only)
Cooling
Unoccupied Free Cooling
Heating
HVACMODE_TEXT_1
HVACMODE_TEXT_2
(table only)
HVACMODE_TEXT_3
(table only)
HV.DN
Remote HVAC Mode Disable
Yes/No
HVACDOWN
forcible
EFF.C
Cool Setpoint in Effect
xxx.x
CSP_EFF
EFF.H
Heat Setpoint in Effect
xxx.x
HSP_EFF
OCC
Currently Occupied
Yes/No
OCCUPIED
forcible
T.OVR
Timed Override in Effect
Yes/No
MODETOVR
LINK
Linkage Active
Yes/No
MODELINK
D.LMT
Demand Limit In Effect
Yes/No
MODEDMDL
C.LOC
Compressor OAT Lockout
Yes/No
COMPLOCK
H.LOC
Heat OAT Lockout
Yes/No
HEATLOCK
E.LOC
Econo Cool OAT Lockout
Yes/No
ECONLOCK
COOL
Cooling Status
COOLDISP
DMD.C
Cooling Demand
xxx.x
^F
COOL_DMD
SA.CP
Supply Air Control Point
xxx.x
dF
SA_CTLPT
SASP
Cool Supply Air Setpoint
xxx.x
dF
SASP
SR.CD
Cool Demand SASP Reset
xxx.x
^F
CD_RESET
SR.RH
Dehumidifying SASP Reset
xxx.x
^F
RH_RESET
F.SPD
Commanded Fan Speed
xxx
%
FANSPEED
CMP.A
Compressor A Feedback
On/Off
COMP_A
TG.A
Compressor A Timeguard
xxx
sec
TIMGD_A
CAPC
Compressor Capacity
xxx
%
CAPACITY
MAX.C
Max Compressor Capacity
xxx
%
MAX_CAPC
forcible
MIN.C
Min Compressor Capacity
xxx
%
MIN_CAPC
LMT.C
Max Capacity In Effect
xxx
%
CAPLIMIT
SST.A
Sat. Suction Temp A
xxx.x
dF
SST_A
SSP.A
Suction Pressure A
xxx.x
psig
SSP_A
SCT.A
Sat. Condenser Temp A
xxx.x
dF
SCT_A
SCP.A
Condenser Pressure A
xxx.x
psig
SCP_A
OFC.1
Outdoor Fan 1 Relay
On/Off
OFC_1
HEAT
Heating Status
HEATDISP
DMD.H
Heating Demand
xxx.x
^F
HEAT_DMD
AVL.H
Available Heating Stages
x
AVLHSTGS
REQ.H
Requested Heating Stages
x
REQHSTGS
MAX.H
Max Allowed Heat Stages
x
MAXHSTGS
forcible
LMT.H
Max Heat Stage In Effect
x
HSTGLIMT
F.SPD
Commanded Fan Speed
xxx
%
FANSPEED
HT.1
Heat Stage 1 Relay
On/Off
HEAT_1
TG.H1
Heat Stage 1 Timequard
xxx
sec
TIMGD_H1
HT.2
Heat Stage 2 Relay
On/Off
HEAT_2
TG.H2
Heat Stage 2 Timequard
xxx
sec
TIMGD_H2
ECON
Economizer Status
ECONDISP
EC.CP
Econo Commanded Position
xxx
%
ECONOCMD
EC.AP
Econo Actual Position
xxx
%
ECONOPOS
EC.MP
Min Position in Effect
xxx
%
MIN_POS
IAQ.S
IAQ Level (switch)
High/Low
IAQIN
IAQ
IAQ Level (sensor)
xxxx
ppm
IAQ
OAT
Outdoor Air Temperature
xxx.x
dF
OA_TEMP
ENTH
Outdoor Enthalpy Switch
High/Low
ENTHALPY
OAQ
OAQ Level (sensor)
xxxx
ppm
OAQ
PE.1
Power Exhaust 1 Relay
On/Off
PE_1
PE.2
Power Exhaust 2 Relay
On/Off
PE_2
HRS
Component Run Hours
STRTHOUR
A1
Compressor A1 Run Hours
xxxxx.xx
hours
HR_A1
forcible
CCH
Crankcase Htr Run Hours
xxxxx.xx
hours
HR_CCH
forcible
IDF
Indoor Fan Run Hours
xxxxx.xx
hours
HR_IDF
forcible
OFC.1
Outdoor Fan 1 Run Hours
xxxxx.xx
hours
HR_OFC_1
forcible
HT.1
Heat Stage 1 Run Hours
xxxxx.xx
hours
HR_HTR_1
forcible
HT.2
Heat Stage 2 Run Hours
xxxxx.xx
hours
HR_HTR_2
forcible
PE.1
Power Exhaust1 Run Hours
xxxxx.xx
hours
HR_PE_1
forcible
PE.2
Power Exhaust2 Run Hours
xxxxx.xx
hours
HR_PE_2
forcible
ALRM
Alarm Relay Run Hours
xxxxx.xx
hours
HR_ALM
forcible