C-1
A P P E N D I X C
Modbus Output
Registry Entities and Values
This appendix contains FlowShark
®
Modbus output registry entities
and values.
Description
Profile Entity
®
Units of
Measure
Registers
Flow
FLOW1
MGD
40001-40002
Peak Velocity
RAWVEL
FPS
40003-40004
UniDepth
UNIDEPTH
Inches
40005-40006
Ultrasonic Depth
UDEPTH
Inches
40007-40008
Unadjusted Pressure
Depth
N/A
Inches
40009-40010
Ultrasonic Range 0
U2
Inches
40011-40012
Ultrasonic Range 1
U3
Inches
40013-40014
Ultrasonic Range 2
U4
Inches
40015-40016
Ultrasonic Range 3
U5
Inches
40017-40018
Rain Intensity
RAINI
Inches/Unit
Time
40019-40020
Ultrasonic Range
(Arbitrated)
Diagnostic
Inches
40021-40022
Ultrasonic
Temperature
Diagnostic
Degrees F
40023-40024
Monitor Voltage
BTYVOLT
Volts
40025-40026
QThreshold
QTHRESHOLD
MGD
40027-40028