Alpha cable type – ADS Environmental Services FlowShark QR 775002 A4 User Manual
Page 198

Analog Input/Output Installation and Configuration 8-11
ALPHA Cable Type
Pin Pair Wire Color
1
Function
Notes
A
1
Shield
Analog Input Channel #1
Ground
Connect to shield of end-
run cable
B
1
Red
Channel #1 4-20mA Input +
C
1
Black
Channel #1 4-20mA Input -
D
2
Shield
Analog Input Channel #2
Ground
Connect to shield of end-
run cable
E
2
White
Channel #2 4-20mA Input +
F
2
Black
Channel #2 4-20mA Input -
G
3
Black
0 - 5 VDC Output #1
Jumper Selectable,
default is 4-20mA output
H
4
Blue
+24VDC Power (for Output
#1
2
+24VDC not needed if
user supplies loop power
J
4
Black
Output #1 Ground
K
3
Green
4-20mA, Output #1
L
5
Black
0 - 5 VDC Output #2
Jumper Selectable,
default is 4-20mA output
M
6
Yellow
+24VDC Power (for Output
#2)
2
+24VDC not needed if
user supplies loop power
N
6
Black
Output #2 Ground
P
N/C
N/A
N/A
R
5
Brown
4-20mA, Output #2
1
This represents the color wire inside the associated pair.
2
+24VDC power for outputs 1 and 2 can be common if isolated operation is not required.