DeviceNet Communications Module

8.6

ControlLogix Example

The following common Tags are used:

The following Tags are used for Drive 0:

The same type of Tags are also used for Drive 1 through Drive 4.

Main Routine

The Main Routine tells the 1756-DNB scanner to run, reads the
network Input Image from the scanner, calls the various drive
control subroutines, and writes the network Output Image to the
scanner. See figure 8.6.

Tag Name

Type

Description

Local : 3 : I

AB: 1756_D...

1756-DNB I/O

Local : 3 : O

AB: 1756_D...

Local : 3 : 5

AB: 1756_D...

Drive Input Image

INT [10]

Input Image Table

Drive Output Image

INT [10]

Output Image Table

Tag Name

Type

Description

Drive 0 Command Stop

BOOL

Logic Command bit 0 (STOP)

Drive 0 Command Start

BOOL

Logic Command bit 1 (START)

Drive 0 Command Jog

BOOL

Logic Command bit 2 (JOG)

Drive 0 Command Clear Faults

BOOL

Logic Command bit 3 (CLEAR
FAULTS)

Drive 0 Command Forward

BOOL

Logic Command bit 4
(FORWARD)

Drive 0 Reference

INT

Speed Reference

Drive 0 Status Ready

BOOL

Logic Status bit 0 (READY)

Drive 0 Status Active

BOOL

Logic Status bit 1 (ACTIVE)

Drive 0 Status Forward

BOOL

Logic Status bit 3 (FORWARD)

Drive 0 Status Faulted

BOOL

Logic Status bit 7 (FAULT)

Drive 0 Status At Reference

BOOL

Logic Status bit 8 (AT SPEED)

Drive 0 Feedback

INT

Speed Feedback

Perform Parameter Read 0

BOOL

Initiates the parameter read

Parameter RD Value 0

INT

Read value of the parameter

Parameter RD Message 0

MESSAGE

Get_Attribute_Single (Read)

Perform Parameter Write 0

BOOL

Initiates the parameter value

Parameter WR Value 0

INT

Write value to the parameter

Parameter WR Message 0

MESSAGE

Set_Attribute_Single (Write)