B-2

DeviceNet Communications Module

Displays the Single- or Multi-Drive operating mode selected with
jumper on the module.

Sets the node address used by the drive after a reset or power
cycle. This setting is used when all of the module DIP switches are
in the CLOSED position (all 0s).

Displays the DeviceNet node address currently being used by the
module.

Sets the DeviceNet data rate after a reset or power cycle. This
setting is used when all of the module DIP switches are in the
CLOSED position (all 0s).

1

Mode

Range:

0 = Single Drive
1 = Multiple Drive

Default:

0 = Single Drive

Type:

Read Only

Reset Required: N/A

2

DN Addr Cfg

Range:

0 to 63

Default:

63

Type:

Read/Write

Reset Required: Yes

3

DN Addr Act

Range:

0 to 63

Default:

63

Type:

Read Only

Reset Required: N/A

4

DN Rate Cfg

Range:

0 = 125 kbps
1 = 250 kbps
2 = 500 kbps
3 = Autobaud

Default:

3 = Autobaud

Type:

Read/Write

Reset Required: Yes