beautypg.com

Rockwell Automation DeviceNet Communications Module User Manual

Page 44

background image

5-4

DeviceNet Communications Module

Step 8. Select the type(s) of data exchange (Polled, Change of

State, and/or Cyclic). In our example, we selected Polled.

Step 9. Type the number of bytes that are required for your I/O in

the Input Size and Output Size boxes. The size will
depend on the I/O that you enabled in the module. This
information can be found in DSI I/O Actual (16) in the
module. Table 5.1 shows common configuration Input/
Output sizes.

In our example, we typed 4 in the Input Size and Output
Size boxes because the Mode Jumper on the module is
set to “Single” (default) and DSI I/O Active (16) is set to
“Drive 0” (only one drive being connected). Logic
Command/Reference uses 4 bytes and Logic Status/
Feedback uses 4 bytes.

Step 10. Set the scan rate. See table 5.2.

Step 11. Click OK. If you changed any settings, a Scanner Applet

asks if it is OK to unmap the I/O. Click Yes to continue.
The Edit I/O Parameters dialog box closes and then the
Scanner Module dialog box (figure 5.2) reappears. You will
map the I/O in the next section in this chapter.

Table 5.1 – Input/Output Size Configuration

Input

Size

Output

Size

Logic

Command/

Status

Reference/

Feedback

Parameter 16 -

(DSI I/O Active)

Parameter 1 -

(Mode)

4

4

Drive 0

Single

8

8

Drives 0-1

Multi-Drive

12

12

Drives 0-2

16

16

Drives 0-3

20

20

Drives 0-4

Table 5.2 – Scan Rates

Data Exchange

Rate to set

Polled

Polled Rate

Change of State

Heartbeat Rate

Cyclic

Send Rate