7-14

DeviceNet Communications Module

Ladder Logic Program

Important: To originate a scanner transaction, use a copy operation

to M0:[slot number]:224. Then, use a copy operation to
read M1:1.224 for the result. If more than one message
is enabled, use the TXID to determine which message
you are reading.

For the I/O message portion of this sample ladder program, see
figure 6.6.

Figure 7.9 – Sample SLC Ladder Logic Program

Explicit Messaging Example

When B3:2/0 is set ON, this rung will copy the 32 words of Explicit Message from
the buffer at N9:10 to the M0 File Explicit Message buffer. The scanner will send
the message out over DeviceNet.

0014

B3:2

0

COP

Copy File
Source

#N9:10

Dest

#M0:1.224

Length

32

COP

U

B3:2

0

When I:1.0/15 is ON (response to the explicit message is available), the response
message is copied into N9:50. A "4" command is copied into the M0 file, which
commands the 1747-SDN to discard the response data so that the buffer can be used
for the next message.

0015

I:1

15

1747-SDN

COP

Copy File
Source

#M1:1.224

Dest

#N9:50

Length

32

COP

EQU

Equal
Source A

N9:10

257 <
Source B

N9:50

257 <

EQU

MVM

Masked Move
Source

N9:0

4<
Mask

00FFh

255 <
Dest

M0:1.224

?<

MVM

0016

END