Configuring the DeviceNet Module

4-7

4.4

Setting the Node Address

The value of DN Addr Cfg (2) determines the node address if all of
the module DIP switches are in the CLOSED position (all 0s). We
recommend that you do not use node address 63 because all new
devices use it as the default address. Address 63 is also used for
Automatic Device Recovery.

Step 1. Set the value of DN Addr Cfg (3) to a unique node address.

See figure 4.6.

Step 2. Reset the module. Refer to section 4.9, Resetting the

Module, for this procedure.

If you are using RSNetWorx for DeviceNet, select Network >
Single Browse Path
to see the new address; then delete the old
address.

4.5

Setting the Data Rate

The value of DN Rate Cfg (4) determines the DeviceNet data rate if
all of the module DIP switches are in the CLOSED position (all 0s).
The Autobaud setting will detect the data rate used on the network if
another device is setting the data rate. Your application may require
a different setting.

Step 1. Set the value of DN Rate Cfg (4) to the data rate at which

your network is operating.

Step 2. Reset the module. Refer to section 4.9 for this procedure.

Figure 4.6 – DeviceNet Node Address Screen on an LCD OIM

DN Addr Cfg

Parameter:

#

002

63

VALUE

LIMITS

SEL

Default = 63

Figure 4.7 – DeviceNet Data Rate Screen on an LCD OIM

Value Baud Rate

0

125 kbps

1

250 kbps

2

500 kbps

3

Autobaud (Default)

DN Rate Cfg

Parameter:

#

004

Autobaud

3