Rockwell Automation DeviceNet Communications Module User Manual
Page 81
Using Multi-Drive Mode
8-7
Module Settings for the Example Program
• The Mode Jumper on the module is set to the Multi-Drive
operation position. See section 3.2, Commissioning the Module.
• All DIP switches on the module are set to CLOSED (all 0s). See
section 3.2, Commissioning the Module. The actual node address
will be set via a software parameter.
• The following module parameters are set:
Important: Drive node addresses change only after a power cycle.
Drive Settings for the Program Example
Parameter
Value
Description
02 - (DN Addr Cfg)
1
DeviceNet node address
15 - (DSI I/O Cfg)
4
“Drives 0-4” — 5 drives on 1 node
17 - (Drv 0 Addr)
1
1
Modbus address of Drive 0
18 - (Drv 1 Addr)
2
Modbus address of Drive 1
19 - Drv 2 Addr)
3
Modbus address of Drive 2
20 - (Drv 3 Addr)
4
Modbus address of Drive 3
21 - (Drv 4 Addr)
5
Modbus address of Drive 4
1
The settings for these parameters must match the parameter A104 (Comm
Node Addr) settings in the respective drives.
Parameter
Value
Drive 0
Drive 1
Drive 2
Drive 3 Drive 4
P36 - (Start Source)
5
5
5
5
5
P38 - (Speed Reference)
5
5
5
5
5
A103 - (Comm Data Rate)
4
4
4
4
4
A104 - (Comm Node Addr)
1
1
2
3
4
5
A105 - (Comm Loss Action)
0
0
0
0
0
A106 - (Comm Loss Time)
5
5
5
5
5
A107 - (Comm Format)
0
0
0
0
0
1
The settings for these parameters must match the respective parameter
settings in the module (parameter 17 (Drive 0 Address) through parameter
21 (Drive 4 Address)).