7-12

DeviceNet Communications Module

Ladder Logic Program

Figure 7.8 – Sample PLC-5 Ladder Logic Program

Explicit Messaging Example

When B3:0/0 is set to ON, a one-time BTW sends the explicit message data (starts at N11:0)
to the scanner. The MOV instruction then initializes the first word of the data file that is
used by the BTR instruction in the next rung.

0003

B3:0

0

Send
Explicit
Message

ONS

B3:0

1

EN

DN

ER

BTW

Block Transfer Write
Module Type

1771-SDN DeviceNet Scanner Module

Rack

000

Group

0

Module

0

Control Block

BT20:2

Data File

N11:0

Length

64

Continuous

No

Setup Screen

BTW

MOV

Move
Source

0

0<
Dest

N11:100

257 <

MOV

When the BTW is complete (BT20:2.DN = ON), the CMP instruction compares the first
word of data sent from the scanner to the first word of data sent by the program to the
scanner. When the messaging function is complete, the two words will be equal. The explicit
message response data is stored starting at N11:100.

0004

BT20:2

DN

CMP

Comparison
Expression

N11:100 <> N11:0

CMP

BT20:3

EN

EN

DN

ER

BTR

Block Transfer Read
Module Type

1771-SDN DeviceNet Scanner Module

Rack

000

Group

0

Module

0

Control Block

BT20:3

Data File

N11:100

Length

64

Continuous

No

Setup Screen

BTR

0005

END