Rockwell Automation DeviceNet Communications Module User Manual
Page 103
Troubleshooting the DeviceNet Module and Network
9-7
Events
Many events in the event queue occur under normal operation. If
you encounter unexpected communications problems, the events
may help you or Rockwell Automation personnel troubleshoot the
problem. Table 9.6 lists events that may appear in the event queue:
Table 9.6 – Event Codes and Descriptions
Code
Event Description
0
No Event
Text displayed in an empty event queue entry.
1
Host Sent Reset
The MDI product issued this because it was reset.
2
EEPROM Sum Flt Startup sequence detected corrupt EEPROM
storage.
3
Reserved
4
Control Disabled
Sets the PCCC to zero.
5
Control Enabled
Sets the PCCC timeout to non-zero and sends a
PCCC control command.
6
PCCC IO Time Flt Control by a PCCC device has timed out.
7
Normal Startup
Signifies the first event after a reset or power cycle.
8
Reserved
9
DSI Fault Msg
MDI drive faulted.
10
DN Poll Timeout
DeviceNet did not send an I/O poll message in the
required time interval.
11
DN I/O Too Long
The length of the data from the I/O scanner was too
long.
12
Bad I/O Fragment
An I/O fragment from the scanner arrived out of
sequence.
13
Idle I/O Message
The DeviceNet scanner was placed in the program
mode.
14
Reserved
15
DSI Fault Clear
A drive fault was cleared.
16
DN COS Timeout
I/O data from a DeviceNet COS connection has not
been received in the required interval.
17
DN Poll Allocate
The module was allocated for a DeviceNet polled I/O
connection.
18
DN COS Allocate
The module was allocated for a DeviceNet COS I/O
connection.
19
DN Poll Closed
The DeviceNet master has closed the previous
opened polled I/O connection.
20
DN COS Closed
The DeviceNet master has closed the previously
opened COS I/O connection.
21
DN Dup MAC Flt
The DeviceNet side of the module has failed the
duplicate MAC test.
22
Manual Reset
The module was reset from the “Reset Module”
parameter.
23
Host Timeout
An explicit message to a Drive host has timed out
waiting for a response.