SCANport Command Interface
4-5
Jog Request - If the drive is stopped (disabled via bit 00 of the
command word) and the jog command bit is set true (rising edge) and
there are no faults, the drive will assert the jog reference enabled state
and follow SCANport jog reference command on SCANport adapter
Input Word 2.
The drive will continue to follow the jog reference until the jog is
released. It will then regenerate to a stop.
The manual reference request, bit 11 of the SCANport Logic Command
Word, does not need to be asserted. This will automatically occur
when the jog bit 02 is set.
Fault Clear - If a drive shut down fault has occurred setting the
Drive_Err_Reset bit is required in order to reset the drive shut down
error. The fault cannot be reset unless the fault condition is removed.
Coast Stop Request - If the drive is running and the Coast Stop
Request bit is set the drive power will be removed from the motor and
it will not regenerate. Under this condition the motor will coast until
the friction of the motor and load bring it to a stop.
Refer to the tables below for SCANport I/O key logic commands.
SCANport Input Command Word
SCANport Output Status Word
Bit
Description
Bit
Description
00
Regenerative Stop Request
00
Drive Enabled
01
Start Request
01
Auto Reference Enabled
02
Jog Request
02
Rotation Direction
03
Fault Clear
03
Drive OK
04
Coast Stop Request
04
At Zero Speed
05
Parameter Set Select bit 0
05
At Reference Speed
06
Parameter Set Select bit 1
06
Orient complete
07
Parameter Set Select bit 2
07
Reserved
08
Parameter Strobe
08
Brake Solenoid enabled
09
Orient Request
09
Torque greater than Torque Limit
10
Home Request
10
High Winding Selected
11
Manual Reference Select
11
Low Winding Selected
12
Reserved
12
Shut Down Fault
13
Reserved
13
Reserved
14
Reserved
14
Reserved
15
Reserved
15
Manual Reference Selected