Scaling of auto velocity analog reference, Scaling of auto velocity analog reference -14 – Rockwell Automation 8720MC Drives Integration Manual User Manual
Page 46

Publication 8720MC-IN002A-EN-P — December 2002
2-14
Commissioning Your 8720MC Analog Drive
Refer to the tables below for the linking relationship between the
8720MC I/O event variables and the digital output parameters.
Scaling of Auto Velocity
Analog Reference
This section provides the information you need to scale an auto
velocity analog reference. The default setting is 1000 rpm/10V.
To change the scale factor for the auto velocity analog reference,
perform the following procedure:
1. At the HIM, press the escape key get to the top level display then
depress ENTER. A message similar to the following appears:
2. Press either the up or down arrow key until the following appears:
3. Press ENTER. Press either the up or down arrow key until the
following appears:
Sinks
Typical Sources
Parameter
Number
Parameter
Parameter
Number
Parameter
663
Digital_Output_2
Link
330
At Programmed Speed
664
Digital_Output_3
331
Zero Speed
665
Digital_Output_4
332
Motor Speed Below Threshold
666
Digital_Output_5
334
Torque Above Limit
667
Digital_Output_6
335
Velocity Above Limit
668
Digital_Output_7
336
In Position
669
Digital_Output_8
339
Speed Below Minimum
670
Digital_Output_9
340
Speed Above Maximum
671
Digital_Output_10
526
High Winding Enable
527
Low Winding Enable
528
Enable Brake Solenoid
529
Auto Reference Enabled
530
Manual Mode Selected
583
Orient Complete
615
Shut Down Error
Choose Mode
Display
Choose Mode
Program
Choose File
I/O Interface