beautypg.com

Rockwell Automation 8720MC Drives Integration Manual User Manual

Page 60

background image

Publication 8720MC-IN002A-EN-P — December 2002

3-6

Troubleshooting Your 8720MC Servo Drive

DriveHardFault

(EEprom Init)

Base driver board hardware Failure

Fatal error - replace base driver board

DriveHardFault

(CPLD Load)

Control board hardware Failure

Fatal error - replace control board

DriveHardFault

(IDMA Load)

Control board hardware Failure

Fatal error - replace control board

DriveHardFault

(CAN Init)

Control board hardware Failure

Fatal error - replace control board

DriveHardFault

(SERCOS Init)

Control board hardware Failure

Fatal error - replace control board

DriveHardFault

(Task Init)

Control board software error

Fatal error - replace control board

DriveHardFault

(Objects Init)

Control board software error

Recall parameters, save to non volatile memory, recycle
power or reset the drive. If this fails to produce positive
results replace the control board.

DriveHardFault

(NV Mem Init)

Control board software error

Recall parameters, save to non volatile memory, recycle
power or reset the drive. If this fails to produce positive
results replace the control board.

MotFeedbackFault

(Fdbk Watch dog)

The feedback processor has faulted

Fatal error - replace control board

MotorOvertempFault

(Motor 1 Overtemp)

The motor over temperature switch has
tripped

Allow motor to cool down and investigate the cause of
the motor overload.

DriveHardFault

(SCANport Comm)

The controlling HIM has lost communication
with the drive.

Investigate the SCANport cable and make sure it is
properly connected

SERCOSFault

(SERCOS Ring Flt))

The SERCOS ring is not active after being
active and operational.

Check that the fiber-optic cable is present and
connected properly.

(No Fault)

No fault message appears in the fault que
when there are no faults

No action is needed

Fault Message RSLogix
(HIM)

Probable Cause/Drive Response

Corrective Actions