beautypg.com

Rockwell Automation 7000 PowerFlex Medium Voltage (B Frame) Commissioning - ForGe (PanelView 550) User Manual

Page 99

background image

Rockwell Automation Publication 7000-IN006B-EN-P - May 2013

95

Commissioning the Drive Chapter 5

4. Record the value of the rectifier input voltage by looking at parameter Rec

Input Voltage (P696); for example,

V

in0

.

5. For SCR drives set parameter Idc Command Test in Current Control to

0.800 pu. For AFE drives set the parameter to 0.300 pu; for example, I

dc

.

6. Start the drive and wait for a few seconds for steady state conditions to be

established.

7. Record the value of the rectifier input voltage by looking at parameter Rec

Input Voltage (P696); for example, V

in1

.

8. Calculate the value of input impedance for AFE drives as follows:

C

in

is the value of input filter capacitor given by Line Filter Cap (P133).

9. Calculate the value of input impedance for SCR drives as follows:

10. Stop the drive. Set the Operating Mode parameter to Normal and Idc

Command Test to zero.

T DC Link (P#115) Manual Tuning

Determine an appropriate value for the T DC Link parameter from the current
regulator step response while operating in DC Current test mode. Use the
following procedure:

1. Ensure you set all parameters in the Drive Hardware and Motor Ratings

groups to the correct values. Otherwise, the calculated value of parameter
T DC Link in Current Control will be incorrect.

2. Set parameter Operating Mode in the Feature Select to DC Current to

enter the test mode.

Figure 54 - Current control parameter screen

3. Set parameter Idc Test Command in Current Control to 0.225 pu for AFE

rectifier drives and 0.400pu for SCR drives.

drives

for

V

V

C

I

V

V

L

in

in

in

dc

in

in

in

PWM

)

(

1

0

1

0

+

=

drives

SCR

for

I

V

V

L

dc

in

in

in

)

(

3

1

0

=