Commissioning the Drive Chapter 5

Control Power Tests

Although there are a variety of options available to customers that will effect the
control power distribution within the drive, the input will always be as illustrated
below:

Figure 42 - Control power distribution

Three-Phase Input

In the 3-phase input configuration, the customer supplies 3-phase control power
into the disconnect switch (Labeled DS1 on the Electrical Schematics). From
that point, the power is distributed to the 3-phase fan and to the power supplies
through a single phase CPT. The output of the single phase CPT powers all the
power supplies and controls within the drive. The 3-phase control should be
measured at the input to DS1. If the rating matches the designation on the
electrical schematic, it is acceptable to apply control power to the drive. Take
necessary measures to rectify the control power level in the event that it does not
meet the design specifications.

20V

ISOLATED

GATE DRIVER

POWER SUPPLY

Single Phase

AC/DC

Converter

56V

1000W or

1500W

+5V-LOGIC

+/-15V-LOGIC

+/-24V-HECS

+24V-ISOLATORS

+24V-XIO

20V

DC/DC

CONVERTER

Fan

SENSE
CABLE

DC Fail

120V

Single

phase

Grounded

Neutral

CB1

Customer

supplied

3-ph

C hold-up

CPT1

Optional

1-ph

&

Remote

I/O

PV550

IMPORTANT

Prior to energizing the drive, verify that the control power feeding into the
input breakers is rated as designated on the electrical diagram.