Control power tests, Three-phase input – Rockwell Automation 7000 PowerFlex Medium Voltage (B Frame) Commissioning - ForGe (PanelView 550) User Manual
Page 71

Rockwell Automation Publication 7000-IN006B-EN-P - May 2013
67
Commissioning the Drive Chapter 5
Control Power Tests
Although there are a variety of options available to customers that will effect the
control power distribution within the drive, the input will always be as illustrated
below:
Figure 42 - Control power distribution
Three-Phase Input
In the 3-phase input configuration, the customer supplies 3-phase control power
into the disconnect switch (Labeled DS1 on the Electrical Schematics). From
that point, the power is distributed to the 3-phase fan and to the power supplies
through a single phase CPT. The output of the single phase CPT powers all the
power supplies and controls within the drive. The 3-phase control should be
measured at the input to DS1. If the rating matches the designation on the
electrical schematic, it is acceptable to apply control power to the drive. Take
necessary measures to rectify the control power level in the event that it does not
meet the design specifications.
20V
ISOLATED
GATE DRIVER
POWER SUPPLY
Single Phase
AC/DC
Converter
56V
1000W or
1500W
+5V-LOGIC
+/-15V-LOGIC
+/-24V-HECS
+24V-ISOLATORS
+24V-XIO
20V
DC/DC
CONVERTER
Fan
SENSE
CABLE
DC Fail
120V
Single
phase
Grounded
Neutral
CB1
Customer
supplied
3-ph
C hold-up
CPT1
Optional
1-ph
&
Remote
I/O
PV550
IMPORTANT
Prior to energizing the drive, verify that the control power feeding into the
input breakers is rated as designated on the electrical diagram.