Rockwell Automation 7000 PowerFlex Medium Voltage (B Frame) Commissioning - ForGe (PanelView 550) User Manual
Page 127

Rockwell Automation Publication 7000-IN006B-EN-P - May 2013
123
General Reference
Appendix A
Damper opened
VT
40
110
100
Normal
No
CHIPPER (WOOD)—
starting empty
CT
50
40
200
Contact factory
No
COMPRESSORS
Axial-vane, loaded
VT
40
100
100
Normal
No
Reciprocating, starting
unloaded
CT
100
100
100
Contact factory
Yes
Conveyors
Belt type, loaded
CT
150
130
100
Heavy
Yes
Drag type
CT
175
150
100
Contact factory
Yes
Screw type, loaded
CT
200
100
100
Contact factory
Yes
EXTRUDERS (rubber
or plastic)
CT
150
150
100
Contact factory
Yes
FANS (centrifugal, ambient)
Damper closed
VT
25
60
50
Normal
No
Damper open
VT
25
110
100
Normal
No
FANS (centrifugal, hot gases)
Damper closed
VT
25
60
100
Normal
No
Damper open
VT
25
200
175
Contact factory
No
FANS (propeller,
axial flow)
VT
40
110
100
Normal
No
KILNS (rotary,
loaded)
CT
250
125
125
Contact factory
Yes
MIXERS
Chemical
CT
175
75
100
Contact factory
Yes
Liquid
CT
100
100
100
Heavy
Yes
Slurry
CT
150
125
100
Heavy
Yes
Solids
CT
175
125
175
Contact factory
Yes
PULPER
VT
40
100
150
Contact factory
No
PUMPS
Centrifugal, discharge
open
VT
40
100
100
Normal
No
Oil field Flywheel
CT
150
200
200
Contact Factory
Yes
Propeller
VT
40
100
100
Normal
No
Fan Pump
VT
40
100
100
Norma
No
Reciprocating /
Positive Displacement
CT
175
30
175
Contact factory
Yes
Screw type, started dry VT
75
30
100
Normal
No
Screw type, primed,
discharge open
CT
150
100
1000
Heavy
Yes
Slurry handling,
discharge open
CT
150
100
100
Heavy
Yes
Application
Load
Torque
Profile
Load Torque as Percent of Full-Load Drive Torque
Required Drive
Service Duty
Rating
Tachometer
Required for
Extra Starting
Torque?
Break-away
Accelerating
Peak Running