Rockwell Automation 7000 PowerFlex Medium Voltage (B Frame) Commissioning - ForGe (PanelView 550) User Manual
Page 59
Rockwell Automation Publication 7000-IN006B-EN-P - May 2013
55
Commissioning the Drive Chapter 5
1. Lock out and isolate the drive from medium voltage. Verify with a hot stick
that there is no medium voltage present.
2. Determine that the key interlock is correctly aligned by securely bolting
the medium voltage doors of the cabinet closed and removing the key from
the lock. The key should turn easily; if any force is required to turn the key,
the deadbolt alignment requires adjustment.
3. Open the doors of the cabinet and inspect the key assembly. Place high
visibility grease on the pins of the deadbolt counterpart. The factory
recommends using yellow torque sealant, however if it is unavailable
almost any grease will do. (See
Figure 31 - Deadbolt counterpart mounted to cabinet
4. Bolt the cabinet door closed so the pins on the dead bolt counterpart make
contact with the deadbolt assembly. Doing so should leave two marks of
torque sealant or grease on the assembly where the pins made contact (see
).
5. Slightly loosen the adjustment bolts on the counterpart and make the
necessary movements on the counterpart to ensure that the pins align with
the landing plates on the deadbolt assembly. As the amount of counterpart
movement required is an estimate, it may take a couple attempts to
properly align the assembly.
6. Clean the torque seal/grease from the key interlock once finished aligning
the counterpart.
Once properly aligned, the key should turn freely when the cabinet door is fully
bolted shut. If the key does not function when the door is tightly bolted closed,
adjustments will have to be made to the depth of the counterpart. This can be
done by adding shims on the landing plate where the counterpart is mounted.
Place grease on
deadbolt pins here.