Chapter 5 Commissioning the Drive

Bypass Contactor Closures

Sample Waveforms

Ch1: Bypass Contactor Close Command (BPC output at ACB, J1-12 & 402)

Ch2: Actual Closure of Bypass Contactor (using 9V battery across contactor
vacuum bottles)

Figure 65 - Sample waveform: Bypass contactor closures

Synchronous Transfer Test: Verify Sync Lead Angle

While simulating a synchronous transfer to determine the best lead angle:

• ensure you have configured and armed the Diagnostic Trend.
• capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB

test point “Vuvs”.

• capture and trigger on falling edge of the DC Link current waveform at

ACB test point “Idc1”.

• label the waveforms as “Vuv”, “Vuvs” and “Idc1”.
• save the worksheet as “Drift @ 15 Degree Lead Angle”, for example.

Table 7 - Oscilloscope Settings

Oscilloscope

Time Base

Wave Form

Test-Point

Waveform
Label

Chan. 1

10ms/div.

DC Link Current

Idc1

Idc1

Chan. 2

Motor Voltage

Vuv

Vuv

Chan. 3

Bypass Line
Voltage

Vuvs

Vuvs