Commissioning the Drive Chapter 5

Line Terminal Resistance Measurements

Measuring the resistance between the drive line cable terminals will quickly
identify if there is inter-wiring between the 0

º, +20º, and -20º bridges in the

isolation transformer.

Figure 50 - Line terminal designations

There are low resistances between phases through a transformer winding and a
high resistance between transformer windings. Therefore, the expected resistance
measurements are listed in the table below:

If the measurement results are not as described above, the inter-wiring between
the isolation transformer and drive needs to be re-inspected.

Terminal Measurement Points

Expected Resistance

2U -> 2V -> 2W

Approximately 0

3U -> 3V -> 3W

Approximately 0

4U -> 4V -> 4W

Approximately 0

#U -> #V -> #W

Approximately

2U

2V

2W

3W

3V

3U

4W

4V

4U

2U

2V

2W

3W

3V

3U

4W

4V

4U