Rockwell Automation 47C626 AutoMax Programming Executive V4.2 User Manual
Page 90
6Ć4
AutoMax Processor Module instruction manual (JĆ3650)
for additional information.
M/N 57C404 Network Module
If you are adding a Network module, you will be prompted
for a Network" name in addition to the drop number and
depth parameters specified in the Network module
instruction manual. The Network is a single letter code that
serves as the name for the network.
M/N 57C440 Ethernet Module
If you are adding an Ethernet module, you will be prompted
for a logical slot number (the actual slots where Multibus will
access the module) when you add the module to a physical
slot in the rack. The logical slot" is either 2 and 3 or 4 and 5.
Two slots are needed because the module has 128K of
memory and each logical rack slot can access only 64K.
Note that there are explicit restrictions about slot location in
the Ethernet module manual.
M/N 57C413 Common Memory Module (128K)
M/N 57C423 Common Memory Module (256K)
A Common Memory module can be added to slot 0 in the
rack, where it provides storage for common memory
variables and bus arbitration for multiple Processor
modules. If M/N 57C413 is being used, slot 1 must contain
a Processor module, an Ethernet module (configured to
use logical slots 2Ć3 or 4Ć5), or be empty, because 2
logical slots are required by the Common Memory
module. If M/N 57C423 is being used, slots 1Ć3 must
contain Processor modules, an Ethernet module
(configured to use logical slots 4Ć5), or be empty because
4 logical slots are required by the M/N 57C423 Common
Memory module.
Either version of the Common Memory module can be
used in other evenĆnumbered slots in the rack for memory
storage, but in this case it must be added to the rack as
two M/N GEN32K generic modules (see section 6.3). Note
that M/N 57C423 provides 128K of memory storage, the
same as M/N 57C413, when used in an evenĆnumbered
slot.
M/N 57C416 Remote I/O Interface Module
See section 6.2 for additional information required to
configure the remote I/O system after you have added the
Remote I/O module.
Foreign Module or Other Unsupported Module
If the module you want to add is not supported, i.e., not on
the list of available modules, see section 6.3.
M/N 57C418 AB Interface Module or
M/N 57C417 AutoMate Interface Module
If you are adding an AB Interface module or AutoMate
Interface module, you should enter the drop number as a
decimal value. (The same decimal number must be
physically set on the faceplate on the actual module.) The
module will convert switch settings to octal values internally.
M/N 57C429 RĆNet Network Interface Module
If you are adding an RĆNet Interface module, you must
enter the node number as a hexadecimal value. (The