beautypg.com

Rockwell Automation 47C626 AutoMax Programming Executive V4.2 User Manual

Page 90

background image

6Ć4

AutoMax Processor Module instruction manual (JĆ3650)

for additional information.
M/N 57C404 Network Module

If you are adding a Network module, you will be prompted

for a Network" name in addition to the drop number and

depth parameters specified in the Network module

instruction manual. The Network is a single letter code that

serves as the name for the network.
M/N 57C440 Ethernet Module

If you are adding an Ethernet module, you will be prompted

for a logical slot number (the actual slots where Multibus will

access the module) when you add the module to a physical

slot in the rack. The logical slot" is either 2 and 3 or 4 and 5.

Two slots are needed because the module has 128K of

memory and each logical rack slot can access only 64K.

Note that there are explicit restrictions about slot location in

the Ethernet module manual.
M/N 57C413 Common Memory Module (128K)

M/N 57C423 Common Memory Module (256K)

A Common Memory module can be added to slot 0 in the

rack, where it provides storage for common memory

variables and bus arbitration for multiple Processor

modules. If M/N 57C413 is being used, slot 1 must contain

a Processor module, an Ethernet module (configured to

use logical slots 2Ć3 or 4Ć5), or be empty, because 2

logical slots are required by the Common Memory

module. If M/N 57C423 is being used, slots 1Ć3 must

contain Processor modules, an Ethernet module

(configured to use logical slots 4Ć5), or be empty because

4 logical slots are required by the M/N 57C423 Common

Memory module.
Either version of the Common Memory module can be

used in other evenĆnumbered slots in the rack for memory

storage, but in this case it must be added to the rack as

two M/N GEN32K generic modules (see section 6.3). Note

that M/N 57C423 provides 128K of memory storage, the

same as M/N 57C413, when used in an evenĆnumbered

slot.
M/N 57C416 Remote I/O Interface Module

See section 6.2 for additional information required to

configure the remote I/O system after you have added the

Remote I/O module.
Foreign Module or Other Unsupported Module

If the module you want to add is not supported, i.e., not on

the list of available modules, see section 6.3.
M/N 57C418 AB Interface Module or

M/N 57C417 AutoMate Interface Module

If you are adding an AB Interface module or AutoMate

Interface module, you should enter the drop number as a

decimal value. (The same decimal number must be

physically set on the faceplate on the actual module.) The

module will convert switch settings to octal values internally.
M/N 57C429 RĆNet Network Interface Module

If you are adding an RĆNet Interface module, you must

enter the node number as a hexadecimal value. (The