Rockwell Automation 47C626 AutoMax Programming Executive V4.2 User Manual

Page 221

background image

BĆ3

13

Runbase boot error

Ć a check on the runbase failed

14

Processor overlap limit exceeded

Ć ran out of processing capacity (time)

15

External watchdog timeĆout detected

Ć another Processor in the same rack stopped

17

Address error detected

Ć caused by a read/write to an invalid address

18

Spurious interrupt or hardware failure

19

Power failure detected

1A

Watchdog on this Processor failed

1b

Hardware event count limit exceeded

Ć too many interrupts set without being

acknowledged

Ć program too long

Ć collective scans too fast

1C

Illegal instruction detected

Ć runbase software fault

Ć bad processor module

Ć bad EPROMs

1d

Privilege violation detected

Ć runbase software fault

Ć bad processor module

1E

UnĆimplemented instruction detected

Ć runbase software fault

Ć bad processor module

1F

Illegal interrupt detected

Ć runbase software fault

Ć bad processor module

31

Bus error

Ć attempt to access invalid address

32

Define channel error

Ć problem in application software

33

Define scan error

Ć hardware fault

34

Memory integrity lost

Ć hardware fault

35

DC drive CML block initialization error

36

Communication between drive Processor and I/O

controller lost

37

DC drive I/O controller runĆtime board error

Ć hardware fault

38

UDC module generated a STOP ALL

39

UDC module interrupt allocation failed

3A

Processor OS incompatible with UDC OS

Corrective action: correct the problem in application software. Try to reset by

cycling power and reĆloading configuration and application tasks. Replace the

Processor module. For error code 31, see JĆ3650; for error code 37, see JĆ3669.

For error code 17: If you define bits in a register that is also defined as a register,

neither the bits nor the register can be forced. For error code 38, examine the

error logs for all UDC tasks in the rack. Error code 38 can be caused by enabling

CCLK on more than one module in the rack. Verify that CCLK is enabled on only

one module in the rack. For error code 39, cycle power to the rack and reĆload

the configuration and application tasks. For error code 3A, check OS

compatibility.