backup, you will need to load the operating system only

when enhancements become available, when you change

the password for the rack using the PWOS.EXE utility

described in 9.2.1, or when a Processor module in the

rack is replaced.

Step 3.

Connect the personal computer to the leftmost AutoMax

Processor in the rack, following the directions in

section 3.3.

Step 4.

Select the system for which you want to load operating

system(s).

Step 5.

Select Load OS Single Rack from the Commands menu.

You will see the following message.
Connect cable to processor. Depress ENTER key when

ready, ESC key to abort.

Step 6.

Press ENTER.

The Programming Executive will establish communication with the

local rack and will determine the type(s) of AutoMax Processors in

the rack. It will also determine whether operating systems are

currently loaded to the Processors in the rack.
The prompts displayed on the screen will depend on your system

configuration and the options you choose as you progress through

the Load Operating System procedure.
Note: If you are loading an operating system to a Processor or UDC

that already contains one, you will be required to enter the rack

password before the operating system can be loaded. Loading the

operating system to an AutoMax Processor or UDC module that

already has one will cause all application tasks in the rack or the

UDC module to be stopped and deleted.