Rockwell Automation 47C626 AutoMax Programming Executive V4.2 User Manual
Page 77

5Ć43
backup, you will need to load the operating system only
when enhancements become available, when you change
the password for the rack using the PWOS.EXE utility
described in 9.2.1, or when a Processor module in the
rack is replaced.
Step 3.
Connect the personal computer to the leftmost AutoMax
Processor in the rack, following the directions in
section 3.3.
Step 4.
Select the system for which you want to load operating
system(s).
Step 5.
Select Load OS Single Rack from the Commands menu.
You will see the following message.
Connect cable to processor. Depress ENTER key when
ready, ESC key to abort.
Step 6.
Press ENTER.
The Programming Executive will establish communication with the
local rack and will determine the type(s) of AutoMax Processors in
the rack. It will also determine whether operating systems are
currently loaded to the Processors in the rack.
The prompts displayed on the screen will depend on your system
configuration and the options you choose as you progress through
the Load Operating System procedure.
Note: If you are loading an operating system to a Processor or UDC
that already contains one, you will be required to enter the rack
password before the operating system can be loaded. Loading the
operating system to an AutoMax Processor or UDC module that
already has one will cause all application tasks in the rack or the
UDC module to be stopped and deleted.