Configuringana-bethernettodh485, Configuring an a-b ethernet to dh485, Preface – Rockwell Automation 9330-CC ControlGuardian User's Guide User Manual
Page 67
![background image](/manuals/580523/67/background.png)
Preface
ControlGuardian User’s Guide
3-36
Configuring an A-B Ethernet to DH485
For information on the configuration characteristics for an Ethernet Device to
DH485, see Table 3.AD.
Table 3.AD
Configuration Characteristics for Configuring an A-B Ethernet to DH485
If you want to:
Press this key:
Assign a unique communication device name (1-8 characters). This
field must be defined for the software to accept the configuration.
You cannot modify this field. The communication device name that
you assign appears at the top of the screen when you use WHO.
F1
Device Name
Assign a description for a communication device (1-50 characters).
You must define this field for the software to accept
the configuration.
F2
Enter Device Description
Select the A-B Ethernet to DH485 option.
F3
Select Interface Hardware
Assign a timeout for processor reply. Available choices are: 15, 20,
25, 30, 35, 40, 45, 50, 55 and 60 seconds. The default is
20 seconds.
F4
Online Wait for Reply
Enter a destination subnet address. The default is 000.000.000.000
To connect to a remote destination subnet, enter the first three
octets of the destination subnet (xxx.xxx.xxx.000).
Note:
Only devices between 0 and 255 on the subnet you specify
can be addressed.
F5
Destination Subnet Mask
Enter the 1785-KA5 DH+ address (0-77 octal).
F7
1785-KA5 Address
Enter a destination link DH+ address (decimal).
F8
Destination Link
Select local Ethernet or Ethernet to DH+. If you select Ethernet to
DH+, you must also specify:
bridge address
(last three digits of the IP address for the EI module)
module type (PLC-5/250 RM or PLC-5/250 KA)
channel (2 or 3)
pushwheel (1- 8, PLC-5/250 KA only)
F9
F5
F4
F3
F2
Local
Bridge Address
Module Type
Channel
Pushwheel