Configuringa6171-idh(dh+), Configuring a 6171-idh (dh+), Preface – Rockwell Automation 9330-CC ControlGuardian User's Guide User Manual
Page 43
Preface
ControlGuardian User’s Guide
3-12
Configuring a 6171-IDH (DH+)
For information on the configuration characteristics for 6171-IDH, see Table 3.H.
Table 3.H
Configuration Characteristics for 6171-IDH (DH+)
If you want to:
Press this key:
Assign a unique communication device name (1-8 characters). This
field must be defined for the software to accept the configuration.
You cannot modify this field. The communication device name that
you assign appears at the top of the screen when you use WHO.
F1
Device Name
Assign a description for a communication device (1-50 characters).
You must define this field for the software to accept
the configuration.
F2
Enter Device Description
Select the 6171-IDH (DH+) option.
F3
Select Interface Hardware
Assign a timeout for processor reply. Available choices are: 15, 20,
25, 30, 35, 40, 45, 50, 55 and 60 seconds. The default is
20 seconds.
F4
Online Wait for Reply
Assign a communication port. Toggle through COM1, COM2, and
user specified. If you choose the user-specified port, you must
enter the serial port I/O address and the interrupt (IRQ). For more
information about specifying a COM port, see page 3-8.
F5
Communications Port
Enter the source station address (0-77 octal).
F1
Ctrl
Computer Station Address