Preface
ControlGuardian User’s Guide
3-28
Configuring a 1784-KTX/KTXD on DH485
For information on the configuration characteristics for 1784-KTX/KTXD on
DH485, see Table 3.V.
Table 3.V
Configuration Characteristics for the 1784-KTX/KTXD on DH485
If you want to:
Press this key:
Assign a unique communication device name (1-8 characters). This
field must be defined for the software to accept the configuration.
You cannot modify this field. The communication device name that
you assign appears at the top of the screen when you use WHO.
F1
Device Name
Assign a description for a communication device (1-50 characters).
You must define this field for the software to accept
the configuration.
F2
Enter Device Description
Select the 1784-KTX/KTXD on DH485 option.
F3
Select Interface Hardware
Assign a timeout for processor reply. Available choices are: 15, 20,
25, 30, 35, 40, 45, 50, 55 and 60 seconds. The default is
20 seconds.
F4
Online Wait for Reply
The 1784-KTX communication card can use any 4KB block of
memory on any 4K boundary between A000 and EF00
(hexadecimal).
F5
KTX Communications
Board Addr
Enter a name for a programming terminal (1-8 characters). This
name appears next to the station number and device on the WHO
active screen.
F6
Term Name
Enter the source station address (decimal).
F1
Ctrl
Computer Station Address