Configuring1784-kl(dh+), Configuring 1784-kl (dh+) – Rockwell Automation 9330-CC ControlGuardian User's Guide User Manual
Page 40

Configuring Communications
3-9
Configuring 1784-KL (DH+)
Use the 1784-KL board to connect a 1784-T45 or -T47 directly to a processor or to
a local DH+ link. The 1784-KL also provides remote DH+ to DH+ programming.
For information on the configuration characteristics for 1784-KL (DH+), see
Table 3.E.
Table 3.E
Configuration Characteristics for 1784-KL (DH+)
If you want to:
Press this key:
Assign a unique communication device name (1-8 characters). This
field must be defined for the software to accept the configuration.
You cannot modify this field once you have saved the configuration.
The communication device name that you assign appears at the top
of the screen when you use WHO.
F1
Device Name
Assign a description for a communication device (1-50 characters).
You must define this field for the software to accept
the configuration.
F2
Enter Device Description
Select the 1784-KL (DH+) option.
F3
Select Interface Hardware
Assign a timeout for processor reply. Available choices are: 15, 20,
25, 30, 35, 40, 45, 50, 55 and 60 seconds. The default is
20 seconds.
F4
Online Wait for Reply
Enter a name for a programming terminal (1-8 characters). This
name appears next to the station number and device on the WHO
active screen.
F6
Term Name
Define the following:
·Network mode (choose between: local, remote, and DH+ routing)
·Local node address (octal)
·Remote address (octal)
·Destination link ID (decimal) for DH+ routing
·Bridge address (octal) for DH+ routing
F9
Network Mode
Enter the source station address (0-77 octal).
F1
Ctrl
Computer Station Address