1785-UM022C-EN-P - February 2008

5-4

Indicator

Color

1

Probable Cause

Recommended Action

Off

Channel disabled

No action required

Configure for ControlNet communication

Steady
Green

Normal operation

No action required

Flashing
Green/Off

Temporary errors

Make sure that the processor is connected to the
ControlNet network with an Allen-Bradley tap.

Check media for broken cables, loose connectors,
missing terminators, etc.

Flashing
Red/Off

Media fault

Make sure that the processor is connected to the
ControlNet network with an Allen-Bradley tap.

Check media for broken cables, loose connectors,
missing terminators, etc.

No other nodes present on network

Add other nodes to the network

Flashing
Red/Green

Incorrect network configuration

Cycle power or reset unit

If fault persists, contact your Rockwell Automation
representative or distributor

1

Definition of terms:
alternating–the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together);

the two indicators are always in opposite states, out of phase

flashing–the indicator alternates between the two defined states (applies to each indicator viewed independent of the other); if both

indicators are flashing, they flash together, in phase

steady–indicator is on continuously in the defined state

A

B

or