beautypg.com

Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual

Page 132

background image

1785-UM022C-EN-P - February 2008

E-2

Fault Codes

205

ControlNet configuration exceeds processor resources.
IMPORTANT: Scheduled connections will be closed. You must cycle
power, save with RSNetWorx, or download the program to reopen
the connections.

Because the configuration software is unable to accurately predict all the
resources that the processor will require to execute your ControlNet
configuration software (based on the relative loading on the processor),
this fault code is used if the processor determines that your
configuration (typically when you accept Channel 2 edits) exceeds the
processor’s available bandwidth.
Typical causes of this error code include:
• receiving data from the ControlNet network faster than the ControlNet

PLC-5 processor can parse it

• performing I/O updates too frequently
• performing immediate ControlNet I/O ladder instructions too

frequently.

See S:74 and S:75 for more information.

• Reduce the number of ControlNet I/O map table

entries. Possible ways to do this include:

- using a discrete rack connection instead of

multiple discrete module connections

- combining multiple I/O racks into a single

I/O rack

- putting peer-to-peer data in contiguous

blocks in the data table so that less send
and receive scheduled messages are
required

• Increase your Network Update Time and/or

increase the Requested Packet Intervals for
scheduled data transfers in your I/O map table.

• Increase your ladder program scan by either

adding more logic or by increasing the
Communications Time Slice (S:77).

• Reduce the number or frequency of immediate

ControlNet I/O ladder instructions that are
performed.

206

This error code is reserved.

Contact your local Rockwell Automation
representative if you get this message.

207

This error code is reserved.

Contact your local Rockwell Automation
representative if you get this message.

208

Too many pending ControlNet I/O connections.

Delete one or more I/O map table entries and
reaccept edits for the ControlNet configuration.

230

System attempted transition to Run mode with processor in Invalid
backup state.

Change from the Invalid backup state to the No
Control backup state before transitioning into Run
mode. Refer to the Invalid backup state
troubleshooting table later in this chapter.

231

Bypassed qualification (may occur during race condition when both
processors attempt to go into Run mode at the same time).

Transition the PLC-5 processors into Run mode
one at a time.

232

Both processors attempted to be primaries.

Check all media for broken cables, loose
connectors, missing terminators, etc..

233

ControlNet configuration invalid on transition into Run mode.

Reconfigure the ControlNet channel.

234

Failed Qualification.

Refer to the qualification major faults
troubleshooting table later in this chapter.

235

Illegal invalid backup state

Cycle power to the processor. If the fault reoccurs,
contact Rockwell Automation Technical Support at
440-646-6800

236

Illegal No Control backup state

Cycle power to the processor. If the fault reoccurs,
contact Rockwell Automation Technical Support at
440-646-6800

237

Illegal Primary/Secondary backup state

Cycle power to the processor. If the fault reoccurs,
contact Rockwell Automation Technical Support at
440-646-6800

238

Incompatible firmware revisions

Install the same series and revision of firmware
into both hot backup PLC-5 processors

239

ControlNet keeper mismatch

Use RSNetworx to make the PLC-5 processor a
valid keeper

This fault code:

Indicates this fault:

Take this corrective action: