beautypg.com

F - controlnet diagnostics file layout, Controlnet diagnostics, File layout – Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual

Page 133: Controlnet diagnostics file layout, Appendix

background image

1785-UM022C-EN-P - February 2008

Appendix

F

ControlNet Diagnostics File Layout

When you specify a Control Diagnostic File in RSNetWorx for the
ControlNet network, the PLC-520C, -5/40C, -5/46C or -5/80C
processor copies the 40 words of diagnostic counters into the
specified integer file.

Twenty-three additional diagnostic counters are available in the
ControlNet diagnostic file. To access these counters, you must first
use RSLogix5 to increase the size of the ControlNet diagnostic
integer file to 63 words.

The layout of the ControlNet diagnostic file is described in the
following table. The processor updates this file once every second.

Field Names

File Offset

1

(word;bits)

Buffer Errors

0;15-00

Last 8 Nodes from which bad packets were received

1-4;

Good Frames Transmitted (center significant byte)

5;07-00

Good Frames Transmitted (least significant byte)

5;15-08

Good Frames Received (least significant byte)

6;07-00

Good Frames Transmitted (most significant byte)

6;15-08

Good Frames Received (most significant byte)

7;07-00

Good Frames Received (center significant byte)

7;15-08

Channel A Errors

8;07-00

Bad Received Frames

8;15-08

Aborted Frames Transmitted

9;07-00

Channel B Errors

9;15-08

NUI Overloads

10;07-00

Highwaters/Out-of-Steps

10;15-08

Blockages

11;07-00

Slot Overloads

11;15-08

Aborted Frames Received

12;07-00

Non-Concurrences

12;15-08

Frames with Duplicate Node Address Received

13;07-00

Lonely Occurrences

13;15-08

Collisions

14;07-00

Noise Hits

14;15-08

Moderators from non-lowmen

15;07-00