Installing Your ControlNet PLC-5 Processor

1-23

This processor’s serial port can support these configurations:

Important: Follow these guidelines:

When Channel 0 is configured for RS-422A compatibility, do not
use terminating resistors anywhere on the link.

When Channel 0 is configured for RS-422A (compatible) and
RS-423, do not go beyond 61 m (approximately 200 ft). This
distance restriction is independent of the transmission rate.

DH+ Programming Cables

Remote I/O Cables

Use 1770-CD or cable for remote I/O. See Inserting/Removing the
Processor into/from the I/O Chassis on page 1-13 for more
information.

ControlNet Cables

Several types of RG-6 quad-shield cable may be appropriate for your
ControlNet installation—depending on the environmental factors
associated with your application and installation site.

Digital Interface

Maximum Cable Length

RS-232C

15 m (approximately 50 ft)

RS-422A (compatible)

61 m (approximately 200 ft)

RS-423

61 m (approximately 200 ft)

When using this

communication card:

Use this cable:

1784-KTX, KTXD

• 1784-CP13

1784-PCMK

• 1784-PCM6
• 1784-PCM5 with 1784-CP7 adapter

1784-PKTX, -PKTXD

• 1784-CP13