beautypg.com

Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual

Page 108

background image

1785-UM022C-EN-P - February 2008

B-8

Processor Status File

201

ControlNet input data missed.
The processor is unable to process incoming data from the network.

Recoverable
Check your network for
missing terminators or other
sources of electrical noise
(see the Industrial
Automation Wiring and
Grounding Guidelines,
publication 1770-4.1).

202

ControlNet diagnostic data missed.

Recoverable
Contact your local Rockwell
Automation representative if
you get this message.

203

ControlNet schedule transmit data overflow.

Recoverable
Contact your local Rockwell
Automation representative if
you get this message.

204

Too many output connections per NUI.

Recoverable
Make scheduled outputs
with short Requested Packet
Intervals longer and reaccept
edits for the ControlNet
configuration.

This
fault
code:


Indicates this fault:


And the fault is: