The fields of the CT data type that you can directly address are:

The CIP Generic and Generic Bi-directional CIO command types
allow you to enter any possible CIP command over the ControlNet
network. This allows the processor to send commands to devices not
listed in the command type list, or to send special CIP commands to
devices. Use of these command types requires specific details of the
device to which the command is being sent.

For more detailed information about writing ladder programs, see
your programming software documentation.

Sending Continuous Messages

If you use continuous mode message instructions, do not toggle the
rung condition unless the continuous message is done or errored.
Once enabled, the continuous message will only stop under the
following conditions:

if a message error is detected

if you reset the message CO bit

if you set the TO status bit

You can change the CO and TO bits through the message block
configuration screen or with ladder logic.

Field

Definition

Location

.EW

Enabled-waiting flag bit

word 0, bit 02

.CO

Continuous control bit

word 0, bit 03

.ER

Errored flag bit

word 0, bit 04

.DN

Done flag bit

word 0, bit 05

.ST

Started flag bit

word 0, bit 06

.EN

Enabled flag bit

word 0, bit 07

.TO

Abort (Time out) control bit

word 0, bit 08

.ERR

Error-code word

word 1

.RLEN

Requested length word

word 2

.DLEN

Done length word

word 3

.FILE

Transfer file number

word 4

.ELEM

Transfer element number

word 5

.DATA[0] through.DATA[15]

Remaining words

words 6 through 21