Installing Your ControlNet PLC-5 Processor

If your remote I/O link:

Use this
resistor
rating:

The maximum number of

physical devices
that you can connect
on the link is:

logical rack
numbers that you
can scan on the

link is:

Operates at 230.4K bit/s

82

Ω

32

16

Operates at 57.6K or 115.2K bit/s, and no devices listed below are linked

Scanners

1771-SN; 1772-SD, -SD2;

1775-SR, -S4A, -S4B;

6008-SQH1, -SQH2

Adapters

1771-AS; 1771-ASB (Series A Only); 1771-DCM

Miscellaneous

1771-AF

Connects to any device listed below:

Scanners

1771-SN; 1772-SD, -SD2;

1775-SR, -S4A, -S4B;

6008-SQH1, -SQH2

Adapters

1771-AS; 1771-ASB (Series A Only); 1771-DCM

Miscellaneous

1771-AF

150

Ω

16

16

Operates at 57.6K or 115.2K bit/s, and you do not require over 16 physical devices

You can install a remote I/O link two ways:
- trunk cable/drop cable--from the drop cable to the connector screw terminals on the remote I/O connectors of the processor
- daisy chain--to the connector screw terminals on the remote I/O connectors of the processor and then to the remote I/O screw terminals of the next remote
I/O device

To connect remote I/O cable, use the Phoenix MTSB2.5/3-ST 3-pin header connector provided in the accessory kit.

1. Run the 1770-CD cable from the processor
to each remote I/O adapter module or processor
in the remote I/O system.

2. Connect the signal conductor with blue
insulation to the 3-pin connector terminal
labeled 1 on the processor and to each
remote I/O adapter module (or PLC-5
adapter) in the remote I/O system.

3. Connect the shield drain wire to the center
terminal of the 3-pin connector.

4. Connect the signal conductor with clear
insulation to the 3-pin connector terminal
labeled 2.

5. Tie-wrap the remote I/O network cable to
the chassis to relieve strain on the cable.

6. Terminate the remote I/O link by connecting
an external terminator resistor between the
remote I/O terminals labeled 1 and 2.

1770-CD

Blue

Shield

Clear

Shield

Clear

Blue

1770-CD

To another I/O
link device

PLC-5/40C, -5/46C,
-5/80C Processor

PLC-5/20C
Processor

82W or
150W
resistor

Terminate both ends of a remote I/O link