Page 127

background image

1785-UM022C-EN-P - February 2008

ControlNet I/O Map-Entry Status Words and Error Codes

D-9

65523

0xFFF3

CONTROLNET TRANSFER
QUEUE FULL

The immediate CIO instruction could
not be executed because the queue
is full.

Edit the ladder program so that the
number of active 1771 READ/WRITE
CIO instructions is equal to or less
than the maximum of 32.

65527

0xFFF7

MODULE TIMED OUT

The target slot is empty.

Insert the proper module in the
correct slot of the target node.

The target slot contains the wrong
module type.

An incorrect module or slot was
entered in the map table.

Edit the I/O map table to show the
correct module type and slot.

65529

0xFFF9

COMMUNICATION ERROR
CAUSED LOSS OF DATA

A communication error between the
adapter and the module caused the
transfer to be aborted.

Make sure that the module is
properly seated in the correct slot of
the target node.

Make sure that the adapter’s power
supply is providing the proper
voltage.

The target slot contains the wrong
module type.

Insert the proper module in the
correct slot of the target node.

An incorrect module or slot was
entered in the I/O map table.

Edit the I/O map table to show the
correct module type and slot.

Decimal
Code

Hex. Code

Error Message

Explanation/Possible Cause(s)

Possible Corrective Action(s)