Planning to Use Your ControlNet PLC-5 Processor

Second Rule of

Module Optimization

Place modules that do not require I/O image table space to the right
in the chassis.

Example 4

To understand how optimization with a ControlNet network preserves
I/O image space, look at the following example system:

The following chart shows how a Remote I/O system compares to
one optimized with a ControlNet network.

If you install the system on a PLC-5/20C processor, the Remote I/O
network option would be out of I/O image space, while the
ControlNet network option would have used only one-third of the
available I/O image space. You must take into account future
expansion when optimizing the I/O.

I = Discrete Input Module
O = Discrete Output Module
ACN = ControlNet adapter
A = Analog Module
PS = Power Supply

Chassis 1

Chassis 2

Chassis 3

ACN

A

A

A

A

A

a

A

PS

A

A

ACN

I

O

O

O

O

O

O

PS

ACN

O

I

I

I

I

I

I

PS

Remote I/O

ControlNet Network

Input

Output

Input

Output

Chassis

Address

Size

Address

Size

Address

Size

Address

Size

1
2
3

I:010
I:020
I:030

8
8
8

O:010
O:010
O:030

8
8
8

I:010
I:011

n/a

1
7
0

O:010
O:017

n/a

7
1
0

Total Used

24 (3 racks)

24 (3 racks)

8 (1 rack)

8

Remaining

0

0

16 (2 racks)

16