4-6

1771 ControlNet Transfers in PIIs and STIs

When a 1771 Read or 1771 Write CIO instruction is encountered in a
PII or STI, the processor resumes execution of lower priority ladder
programs (main logic programs) until the CIO is completed. If you
want the PII or STI to run to completion before returning to your
main logic program, place the CIO instruction inside of a UID/UIE
pair in your PII or STI program file.

Using ControlNet

Immediate Data Input and

Output Instructions

You can use two instructions for immediate data input and output on
a ControlNet network—Immediate Data Input (IDI) and Immediate
Data Output (IDO).

IMMEDIATE DATA INPUT

Data file offset

Length

Destination

IDI

IMMEDIATE DATA OUTPUT

Data file offset

Length

Source

ID0

232

10

N11:232

175

24

N12:175