The following table describes each bit in word 23 (Channel status and
Media bits) of the diagnostic file.

Maximum number of simultaneously open target Message
Router connections (always less than or equal to 32)

53

Accumulated number of target Message Router connection
timeouts

54

Current number of used unconnected clients
(always less than or equal to 8)

55

Maximum number of simultaneously used unconnected clients
(always less than or equal to 8)

56

Accumulated number of unconnected client timeouts

57

Current number of used unconnected servers
(always less than or equal to 20)

58

Maximum number of simultaneously used unconnected servers
(always less than or equal to 20)

59

Accumulated number of unconnected server timeouts

60

Accumulated number of dropped unconnected requests

61

Accumulated number of JITT overruns

62

1

The file offset in the user-specified ControlNet diagnostics file. For example, if you
specified N12, then the Buffer Errors would be located in N12:0, bits 15 - 00.

Bit(s):

Description:

Values:

2 - 0

channel A LED state

000 = off

001 = green

010 = flashing green/off

011 = flashing red/off

100 = flashing red/green

101 = railroading red/off

110 = railroading red/green
111 = red

5 - 3

channel B LED state

6

redundancy warning

0 = normal

1 = non-selected channel is unusable

7

active channel

0 = channel B active

1 = channel A active

8

repeater mode

0 = device set for normal mode

1 = device set for repeater mode

9

channel A media mode

0 = configured for Coaxial

1 = configured for fiber

10

channel B media mode

0 = configured for Coaxial

1 = configured for fiber

15 - 11

reserved

Note: A value of 219 in word 23 indicates that the ControlNet network is not usable.

Field Names

File Offset

1

(word;bits)