Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 135
1785-UM022C-EN-P - February 2008
F-3
The following table describes each bit in word 23 (Channel status and
Media bits) of the diagnostic file.
Maximum number of simultaneously open target Message
Router connections (always less than or equal to 32)
53
Accumulated number of target Message Router connection
timeouts
54
Current number of used unconnected clients
(always less than or equal to 8)
55
Maximum number of simultaneously used unconnected clients
(always less than or equal to 8)
56
Accumulated number of unconnected client timeouts
57
Current number of used unconnected servers
(always less than or equal to 20)
58
Maximum number of simultaneously used unconnected servers
(always less than or equal to 20)
59
Accumulated number of unconnected server timeouts
60
Accumulated number of dropped unconnected requests
61
Accumulated number of JITT overruns
62
1
The file offset in the user-specified ControlNet diagnostics file. For example, if you
specified N12, then the Buffer Errors would be located in N12:0, bits 15 - 00.
Bit(s):
Description:
Values:
2 - 0
channel A LED state
000 = off
001 = green
010 = flashing green/off
011 = flashing red/off
100 = flashing red/green
101 = railroading red/off
110 = railroading red/green
111 = red
5 - 3
channel B LED state
6
redundancy warning
0 = normal
1 = non-selected channel is unusable
7
active channel
0 = channel B active
1 = channel A active
8
repeater mode
0 = device set for normal mode
1 = device set for repeater mode
9
channel A media mode
0 = configured for Coaxial
1 = configured for fiber
10
channel B media mode
0 = configured for Coaxial
1 = configured for fiber
15 - 11
reserved
Note: A value of 219 in word 23 indicates that the ControlNet network is not usable.
Field Names
File Offset
1
(word;bits)