1785-UM022C-EN-P - February 2008

1-8

Installing Your ControlNet PLC-5 Processor

Estimated Battery Lifetimes

Dispose of a Battery

If you need to dispose of a battery, follow the procedures described in
Guidelines for Handling Lithium Batteries, (pub. no. AG-5.4).

Worst-Case Battery-Life Estimates

Processor

Temperature

Power Off 100%

Power Off 50%

Battery Duration

1

PLC-5/20C

60° C

173 days

346 days

70 hours

25° C

1.69 years

3.38 years

14.5 days

PLC-5/40C

60° C

92.5 days

185 days

38 hours

25° C

1.25 years

2.5 years

10.8 days

PLC-5/46C

60° C

92.5 days

185 days

38 hours

25° C

1.25 years

2.5 years

10.8 days

PLC-5/80C

60° C

80 days

160 days

33 hours

25° C

1.18 years

2.36 years

10 days

1

The battery status indicator (BATT) warns you when the battery is low. These durations are based
on the battery supplying the only power to the processor—power to the chassis is off—once the
status indicator first lights.

Follow these precautions to prevent the battery from
exploding. An exploding battery exposes toxic,
corrosive and flammable chemicals and causes burns.

• do not incinerate or expose the battery to high

temperatures

• do not solder the battery or leads

• do not open, puncture or crush the battery

• do not charge the battery

• do not short positive or negative terminals together

ATTENTION

!