ControlNet I/O Map-Entry Status Words and Error Codes

D-7

516

0x0204

UNCONNECTED REQUEST
TIMED OUT

The ControlNet cable from the
originating node to the target node is
broken or disconnected.

Fix and/or reconnect the ControlNet
cable.

The target node is not powered.

Supply power to the target node.

The originator’s and/or the target’s
node number is greater than UMAX.

Reconfigure the ControlNet network
so that the originator’s and target’s
node numbers are less than or equal
to UMAX.

The target node is too busy to
respond.

Reduce the number of unconnected
requests to the target node.

769

0x0301

OUT OF BUFFER MEMORY

The maximum number of
connections to/from this node has
been exceeded.

• If this is an I/O connection, reduce

the number of I/O connections.

• If this is a MSG instruction,

reduce the number of MSG
instructions.

• If this is a CIO instruction, reduce

the number of CIO instructions.

770

0x0302

SCHEDULED BANDWIDTH NOT
AVAILABLE

There are too many words
scheduled for transmission.

Edit the I/O map table to reduce the
number of scheduled words.

The network update time (NUT) is
too small.

Increase the network update time
(NUT).

The originator’s and/or the target’s
node number is greater than SMAX.

Reconfigure the ControlNet network
so that the originator’s and target’s
node numbers are less than or equal
to SMAX.

772

0x0304

NO SCHEDULED
CONFIGURATION

The ControlNet cable from the
originating node to the keeper was
broken or disconnected when the
ControlNet network was configured.

Fix and/or reconnect the ControlNet
cable and reconfigure the ControlNet
network.

The keeper was not powered when
the ControlNet network was
configured.

Supply power to the keeper and
reconfigure the ControlNet network.

The originating and/or target node is
not properly configured to send
scheduled data.

Edit the I/O map table of the
originating and/or target nodes to
send scheduled data.

773

0x0305

SCANNER SIGNATURE
MISMATCH

The ControlNet cable from the
originating node to the keeper was
broken or disconnected when the
ControlNet network was configured.

Fix and/or reconnect the ControlNet
cable. Reconfigure the ControlNet
network by enabling and accepting
edits with RSNetWorx.

The ControlNet processor was not
configured on the current network.

Reconfigure the ControlNet network
by enabling and accepting edits with
RSNetWorx.

The ControlNet network was formed
by joining two existing ControlNet
networks.

Reconfigure the new ControlNet
network by enabling and accepting
edits with RSNetWorx.

Decimal
Code

Hex. Code

Error Message

Explanation/Possible Cause(s)

Possible Corrective Action(s)