beautypg.com

13 appendix – JUMO 902931 Wtrans Receiver with Wireless Data Transmission Operating Manual User Manual

Page 97

background image

97

13 Appendix

Electrical data

Environmental influences

Case

Voltage supply

AC 110 to 240 V +10/-15 %, 48 to 63 Hz
or AC/DC 20 to 30 V, 48 to 63 Hz

Power consumption

12 VA

Electrical connection

Screw terminals up to 2.5 mm

2

Electrical safety

According to DIN EN 61010, part 1
overvoltage category III,
pollution degree 2,
for installation in a control cabinet according to DIN EN 50178

Galvanic isolation

The voltage supply is galvanically isolated from the analog out-
puts, relays, and interfaces.

Test voltage

AC 3700 V

Ambient temperature range

-20 to +50 °C without condensation
(even with close mounting)

Storage temperature range

-30 to +70 °C

Temperature influence

≤ ±

0.005 %

1

/K;

per K deviation from the reference temperature of 22 °C (

±

3 K)

1

All accuracy specifications in % from the measuring range end value of 20 mA or 10 V.

Resistance to climatic conditions

Rel. humidity

85 % without condensation

Acc. to DIN EN 60721-3-3 3K3

Vibration resistance

Max. 1 g at 10 to 55 Hz according to DIN IEC 60068-2-6

EMC
- Interference emission
- Interference immunity
- Radio frequency spectrum

DIN EN 61326-1
Class A – for industrial applications only –
industrial requirements
ETSI EN 300220-1 and ETSI EN 300220-2

Material

Polyamide

Flammability class

UL 94 V-2

Dimensions with
antenna screw connection
(W × H × D)

22.5 mm × 115.0 mm × 117.8 mm

Mounting

DIN rail 35 mm × 7.5 mm according to EN 60715

Protection type

IP20 according to DIN EN 60529

Installation position

Vertical

Weight

Approx. 200 g