8 configuring the receiver, 3 channel-specific parameters – JUMO 902931 Wtrans Receiver with Wireless Data Transmission Operating Manual User Manual
Page 62

8 Configuring the receiver
62
8.2.3
Channel-specific parameters
Channels 1 to 16
The following table shows the parameters of channel 1 that are to be set. The next table con-
tains the same setting options for channels 2 to 16.
Parameter
Bottom
line
of dis-
play
Top
line
of display
Value range/selection
Wireless telegram
timeout
(Wireless timeout)
01.Tmo
3
2 to 20 transmission intervals
Offset
(actual value correction)
01.OFF
0.00
-99.99 to +99.99
Filter time constant
01.dF
0
0 to 100 s
Decimal place
01.dP
Auto
0
1
2
Automatic point
xxxx.
xxx.x
xx.xx
Customer-specific lin-
earization
01.Lin
Lin
tAb1
tAb2
tAb3
tAb4
Linear
Table 1
Table 2
Table 3
Table 4
Unit
for resistance transmit-
ter, potentiometer, or
voltage transmitter types
01.Un1
0
0 to 16
(0 = none, mm, cm, m, ml, liters,
hl, m
3
, %, °C, °F, ohm, k ohm,
mV, kg, tonnes, free text entry)
Unit
for pressure transmitter
types
01.Un2
1
0 to 6
(0 = mbar, bar, kPa, MPa, psi, %,
free text entry)
Scaling active
01.Sca
OFF
OFF, on
Scale start
01.SLo
0
-9999 to +9999
Scale end
01.SHi
100
-9999 to +9999
Limit value alarm 1
•
Alarm type 1
01.A1m
OFF
LoAL
HiAL
No alarm
Min. alarm
(actual value < limit value 1)
Max. alarm
(actual value > limit value 1)
•
Limit value 1
for alarm type 1
01.A1L
0
-9999 to +9999
Limit value alarm 2
•
Alarm type 2
01.A2m
OFF
LoAL
HiAL
No alarm
Min. alarm
(actual value < limit value 2)
Max. alarm
(actual value > limit value 2)