beautypg.com

HYDAC CS 1000 User Manual

Page 81

background image

ContaminationSensor CS1000

Status messages

HYDAC Filtertechnik GmbH

en

Page 81 / 100

BeWa CS1000 3247149n en 2009-02-04.doc

2009-02-04

LED

Blink code /

Display /

Analog output /

SwitchOut

CS 1000 Status

To do

Error

No.

Red

Firmware error

Reset (re-supply
voltage) or contact
HYDAC

-1 to 19

Red

4.1 mA / 2.05 V*

Open

Communication error Check wiring

-20 to -39

Red

4.1 mA / 2.05 V*

Open

System error

Reset (re-supply
voltage) or contact
HYDAC

-40 to -69

Red

4.1 mA / 2.05 V*

Open

Error during
automatic setting

Reset (re-supply
voltage)
/ check flow
or contact HYDAC.

-70

Red

4.1 mA / 2.05 V*

Open

Error measuring cell
LED

Reset (re-supply
voltage)
/ check flow
or contact HYDAC.

-100