HDA.ISO Signal 1/2/3/4

The current 4 - -20 mA or voltage 2 - 10 V of the output signal is dependent on the
ISO contamination class 0.0 - 24.4 (resolution 1 class) as shown in the table below:

Current I

ISO code

Voltage U

I <4.00 mA

Cable break

U <2.00 V

I = 4.00 mA

ISO 0

U = 2.00 V

I = 4.39 mA

ISO 1

U = 2.20 V

I = 5.20 mA

ISO 2

U = 2.60 V

I = 5.92 mA

ISO 3

U = 2.96 V

I = 6.61 mA

ISO 4

U = 3.30 V

I = 7.28 mA

ISO 5

U = 3.64 V

I = 7.95 mA

ISO 6

U = 3.97 V

I = 8.63 mA

ISO 7

U = 4.18 V

I = 9.25 mA

ISO 8

U = 4.62 V

I = 9.91 mA

ISO 9

U = 4.95 V

I = 10.57 mA

ISO 10

U = 5.28 V

I = 11.23 mA

ISO 11

U = 5.61 V

I = 11.89 mA

ISO 12

U = 5.94 V

I = 12.55 mA

ISO 13

U = 6.27 V

I = 13.20 mA

ISO 14

U = 6.60 V

I = 13.86 mA

ISO 15

U = 6.93 V

I = 14.52 mA

ISO 16

U = 7.26 V

I = 15.20 mA

ISO 17

U = 7.60 V

I = 15.82 mA

ISO 18

U = 7.91V

I = 16.48 mA

ISO 19

U = 8.24 V

I = 17.13 mA

ISO 20

U = 8.56 V

I = 17.79 mA

ISO 21

U = 8.90 V

I = 18.45 mA

ISO 22

U = 8.23 V

I = 19.11 mA

ISO 23

U = 9.56 V

I = 19.82 mA

ISO 24

U = 9.90 V

I = 20.00 mA

ISO 24.28

U = 10.0 V

The current (I) or voltage (U) can be calculated for a given ISO contamination

class as follows:

I = 4 mA + ISO code x (20 mA - 4 mA) / 24.28

U = 2 V + ISO Code x (10 V - 2 V) / 24.28

The ISO contamination class can be calculated for a given current I or voltage U

as follows:

ISO code = (I - 4 mA) x (24.28 / 16 mA)

ISO code = (U - 2 V) x (24.28 / 8 V)