Analog Output (ANAOUT)
HYDAC Filtertechnik GmbH
en
Page 61 / 100
BeWa CS1000 3247149n en 2009-02-04.doc
2009-02-04
HDA.ISO Signal 1/2/3/4
The current 4 - -20 mA or voltage 2 - 10 V of the output signal is dependent on the
ISO contamination class 0.0 - 24.4 (resolution 1 class) as shown in the table below:
Current I
ISO code
Voltage U
I <4.00 mA
Cable break
U <2.00 V
I = 4.00 mA
ISO 0
U = 2.00 V
I = 4.39 mA
ISO 1
U = 2.20 V
I = 5.20 mA
ISO 2
U = 2.60 V
I = 5.92 mA
ISO 3
U = 2.96 V
I = 6.61 mA
ISO 4
U = 3.30 V
I = 7.28 mA
ISO 5
U = 3.64 V
I = 7.95 mA
ISO 6
U = 3.97 V
I = 8.63 mA
ISO 7
U = 4.18 V
I = 9.25 mA
ISO 8
U = 4.62 V
I = 9.91 mA
ISO 9
U = 4.95 V
I = 10.57 mA
ISO 10
U = 5.28 V
I = 11.23 mA
ISO 11
U = 5.61 V
I = 11.89 mA
ISO 12
U = 5.94 V
I = 12.55 mA
ISO 13
U = 6.27 V
I = 13.20 mA
ISO 14
U = 6.60 V
I = 13.86 mA
ISO 15
U = 6.93 V
I = 14.52 mA
ISO 16
U = 7.26 V
I = 15.20 mA
ISO 17
U = 7.60 V
I = 15.82 mA
ISO 18
U = 7.91V
I = 16.48 mA
ISO 19
U = 8.24 V
I = 17.13 mA
ISO 20
U = 8.56 V
I = 17.79 mA
ISO 21
U = 8.90 V
I = 18.45 mA
ISO 22
U = 8.23 V
I = 19.11 mA
ISO 23
U = 9.56 V
I = 19.82 mA
ISO 24
U = 9.90 V
I = 20.00 mA
ISO 24.28
U = 10.0 V
The current (I) or voltage (U) can be calculated for a given ISO contamination
class as follows:
I = 4 mA + ISO code x (20 mA - 4 mA) / 24.28
U = 2 V + ISO Code x (10 V - 2 V) / 24.28
The ISO contamination class can be calculated for a given current I or voltage U
as follows:
ISO code = (I - 4 mA) x (24.28 / 16 mA)
ISO code = (U - 2 V) x (24.28 / 8 V)