The current I or voltage U can be calculated for a given temperature as follows:

I = 4.8 mA + (temperature [°C] + 25) x (19.2 mA - 4.8 mA) / 125

I = 4.8 mA + (temperature [°F] +13) x (19.2 mA - 4.8 mA) / 225

U = 2.4 V + (temperature [°C] + 25) x (9.6 V - 2.4 V) / 125

U = 2.4 V + (temperature [°F] + 13) x (9.6 V-2.4 V) / 225

The temperature in °C or °F can be calculated for a given current I or voltage U as

follows:

Temperature [°C]= ((I - 4.8 mA) x (125 / 14.4 mA)) - 25

Temperature [°F]= ((I - 4.8 mA) x (225 / 14.4 mA)) - 13

Temperature [°F]= ((U - 2.4 V) x (125 / 7.2 V)) - 25