ContaminationSensor CS1000

Analog Output (ANAOUT)

HYDAC Filtertechnik GmbH

en

Page 66 / 100

BeWa CS1000 3247149n en 2009-02-04.doc

2009-02-04

ISO + T (ISO+T)

The ISO+T signal consists of 4 measured values which are transmitted time-coded
with the following time slices:

4,0

2,0

4,1

2,05

I (mA)

U (V)

time (ms)

4,8

2,4

19,2

High

High

Low

Low

9,6

300

3000

3000

3000

1

2

4

6

8

3

5

7

19,5

9,85

4,3

2,15

19,7

9,75

0,0

19,8

9,9

Ti

me

Signal

Size

Signal duration

per pulse

in ms

Current (I) / Voltage (U)

1

Identifier

> 2 µm

300

High / Low

2 Measured

value

> 2 µm

3000

Current/Voltage for measured value

3

Identifier

> 5 µm

300

High / Low / High / Low

4 Measured

value

> 5 µm

3000

Current/Voltage for measured value

5

Identifier

> 15 µm

300

High / Low / High / Low / High / Low

6 Measured

value

> 15 µm

3000

Current/Voltage for measured value

7

Identifier

Temperature

300

High / Low / High / Low / High / Low / High / Low /

High / Low

8 Measured

value

Temperature

3000

Current/Voltage for measured value