Horner APG XL4 OCS User Manual
Page 46
CH.10
MAN0964-01-EN
June 29, 2012
Page 46 of 122
Protection for Inductive Loads – Inductive loads can cause reverse currents when they shut off that can
shorten the life of relay contacts. Some protective measures need to be determined by an engineer.
Below you will find recommendations that will work for many applications. If you have additional
questions on protection from inductive load, consult an application engineer or HEAPG Technical
Support. Details on devices that may protect outputs can be found in MAN0962-01.
Output State on Controller Stop
When the controller is stopped the operation of each output is configurable. The outputs can hold the
state they were in before the controller stopped or they can go to a predetermined state. By default relay
outputs turn off. For more information on stop state see the
Index
for Cscape settings pages.
10.6
Digital Inputs
Note: Refer to the datasheet for XL4 OCS model you are using for details on jumper settings.
Note: The digital inputs on the XL4 OCS are designed for low voltage DC inputs. The inputs are
designed to support both positive and negative input modes. The mode is set by a jumper setting and a
configuration parameter in Cscape. All the inputs on the unit must be configured to the same mode.
Figure 10.7 – Positive and Negative Inputs
In positive logic mode a positive voltage applied to the input will turn the input. The internal design of this
mode is basically a resistor from the input to I/O ground. This mode is sometimes called sourcing.
In negative logic mode, connecting the input to the I/O ground or zero volts will turn the input on. The
internal design of this mode is basically a resistor from the input to the positive I/O voltage (usually 12 or
24 volts). This mode is sometime called sinking.
Some of the digital inputs may support high speed input functional such as counting or frequency
measurement.
10.7
Analog Inputs
Note: See the data sheet for the XL4 OCS model you are using for jumper settings and see the
appropriate page in this manual (see Index) for details on how to use Cscape to configure the digital
filtering.
The analog inputs on the XL4 OCS allow voltage or current measurement from a variety of devices. The
voltage or current mode is set though jumpers on the unit and settings in Cscape. Each channel can be
separately configured for voltage or current mode.
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XL SERIES OCS can be wired for Positive Logic inputs or Negative
Logic inputs.